Herunterladen Inhalt Inhalt Diese Seite drucken

Bosch ARD-AYH12 Installationshandbuch Seite 7

Vorschau ausblenden Andere Handbücher für ARD-AYH12:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

ARD-AYH12
Color
Brown
Purple
Cable Notes:
1.
The individual wires coming out of the reader are color
coded according to the recommended Wiegand standard.
2.
When using a separate power supply for the reader, this
supply and the controller's power supply must have a
common ground.
3.
The cable shield wire on the reader should be attached to
an earth ground (best) or signal ground connection at the
panel or power supply end of the cable. This configuration
is best for shielding the reader cable from external
interference.
OPERATION INSTRUCTIONS
The reader should be tested after wiring it to a power supply
and the controller.
Do this by performing the following steps:
1.
Power up the reader. The LED and beeper will activate
three times. This indicates that the reader is working
properly.
2.
Present the appropriate type of proximity card to the
reader. The LED will momentarily flash green and a short
beep will be emitted. This indicates that the card was read
properly by the Proximity Card Reader.
3.
After the card data is processed by the controller, the
controller can then turn the LED green. Refer to the
controller description of the LED operation if the reader
LED is controlled by the controller.
Bosch Sicherheitssyteme GmbH
Wiegand Output
LED Control
Tamper
Installation Manual | en
| V 1.2 | 2009.09
7

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis