5. Contacting of the conductor end
The connection element is used for connecting the HVI
the supporting tube and to the air-termination system /metal capping.
If required, the conductor has to be cut to length on site. The HVI
for contacting the connection element as shown in Fig. 9.
Cable shears can be used to cut the HVI
entire coating has to be shortened by 30 mm. The dark-grey coating of the HVI
to be shortened by another 15 mm so that the underlying semiconducting black coating can be contacted
(see Fig. 9). The black coating may not be damaged. The HVI
easily and reliably strip the external sheath and the PE insulation without damaging the copper conductor
underneath it.
It can be used to remove the Semiconducting coating and the PE insulation of HVI and HVI
conductors with an outer diameter of 20 mm.
The connection element has to be rotated to insert the HVI
element. The two threaded pins (thightening torque of 5 Nm) allow for safe contacting. Subsequently,
the heat-shrinkable sleeve is shrinked on (see Fig. 9 on the right).
dark-grey coating
black coating
3 0
Fig. 9
Installation of the connection element / set Part No. 819 299
conductor light to length and to remove the coating. The
®
tightening torque of 5 Nm
threaded pins
m m
spring washer
M12 nut
conductor light to the connecting plate of
®
conductor light has to be prepared
®
®
strip 20 tool (Part No. 597 220) allows to
conductor light into the connection
®
m m
1 0
Ø
12
Page
®
conductor light has
heat-shrinkable sleeve
spring washer
M12 nut
1637_MO_0312_DE_GB_060231