11. DATA TELEGRAM STRUCTURE

a) General information
Telegram mode D pursuant to DIN EN 625056-21,
Baud rate 9600 Baud (Z=5)
Byte format 7E1 (1 starting bit, 7 data bits, even parity, 1 stop bit)

b) Data Telegram Structure

Target / meaning
Manufacturer identification
Property number
Meter state
L1 + Active Power
(current output P1)
L2 + Active Power
(current output P2)
L3 + Active Power
(current output P3)
S Li+ Active Power
(current output sum)
Status information
Factory number
18
OBIS
1-0:0.0.0*255
1-0:1.8.0*255
(effective energy +A)
1-0:21.7.255*255
1-0:41.7.255*255
1-0:61.7.255*255
1-0:1.7.255*255
1-0:96.5.5*255
0-0:96.5.5*255
Comment
See DIN EN62056-21
(20 characters max., e.g. Q3DB3004 V3.02)
max. 20 characters
Is always stored in a resolution of 0.1 mWh
(e.g. 12345678.1234567*kWh – no difference
between 8+0 , 7+1 and 6+2 indicated on the display)
Current output – 6 digits + 2 decimal digits in W
with prefix (-123456.12*W)
Current output – 6 digits + 2 decimal digits in W
with prefix (-123456.12*W)
Current output – 6 digits + 2 decimal digits in W
with prefix (-123456.12*W)
Current output sum – 6 digits + 2 decimal
digits in W with prefix (-123456.12*W)
The status word is defined as one byte and
transmitted in hexadecimal indication
The following assignment applies:
Bit[7] – MSB, 0=idle, 1=above start-up
Bit[6] – is set in case of outage of L1
Bit[5] – is set in case of outage of L2
Bit[4] – is set in case of outage of L3
Bit[3:2] – reserved, always 0
Bit[1] – '1' the telegram is always output synchronously in the
fixed time grid
Bit[0] – '0' no error, '1' – error
Manufacturer number (max. 20 characters)