Herunterladen Inhalt Inhalt Diese Seite drucken

LG PLNWKB000 Installations- Und Benutzerhandbuch Seite 87

Vorschau ausblenden Andere Handbücher für PLNWKB000:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

11) Temperature Higher Limit(Air conditioner), Solar Heat Source Temperature(AWHP)
Input
Output
Valid Range
NV
SNVT_temp_p
12) Temperature Select(AWHP)
Output
Valid Range
NV
SNVT_switch
13) AC Operation(ERV DX), Hot Water Operation(AWHP)
Input
Output
Valid Range
NV
SNVT_switch
Function
Temperature Higher Limit(Air conditioner) input
Using NV
network variable : SNVT_temp_p, nviUp_Tm
Operation
Temperature Higher Limit(Air conditioner) control
Temperature Higher Limit(Air conditioner), Solar Heat
Function
Source Temperature(AWHP) display
Using NV
network variable : SNVT_temp_p, nvoUp_Sol_Tmp
Temperature Higher Limit(Air conditioner), Solar Heat
Operation
Source Temperature(AWHP) monitor
Heat Source Temperature : 0 ~ 255 °C
Function
Temperature Select(AWHP) display
Using NV
network variable : SNVT_switch, nvoFilt_Tmpsel
Operation
Temperature Select(AWHP) monitor
Field
value
state
Function
AC Operation(ERV DX), Hot Water Operation(AWHP) input
Using NV
network variable : SNVT_switch, nviIDUrun_HW
AC Operation(ERV DX), Hot Water Operation(AWHP)
Operation
control
Function
AC Operation(ERV DX), Hot Water Operation(AWHP) displa
Using NV
network variable : SNVT_switch, nvoIDUrun_HWEn
AC Operation(ERV DX), Hot Water Operation(AWHP)
Operation
monitor
Field
value
state
Operation
Temperature Higher Limit : 18 ~ 30 °C
Operation
not used (set in 0 % usually)
0 = Air (AWHP)
1 = Pipe Out (AWHP)
Operation
not used (set in 0 % usually)
0 = OFF
1 = ON
77
HINWEISE

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Plnwkb100

Inhaltsverzeichnis