Herunterladen Inhalt Inhalt Diese Seite drucken

LG PLNWKB000 Installations- Und Benutzerhandbuch Seite 108

Vorschau ausblenden Andere Handbücher für PLNWKB000:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

98
HINWEISE
■ AHU General input/output
1) Total OnOff (AHU)
Output
Valid Range
NV
SNVT_switch
2) Total Temperature (AHU)
Output
Valid Range
3) Temperature Unit (AHU)
Input
Output
Valid Range
NV
SNVT_switch
Function
Using NV
Operation
Field
value
state
Function
Using NV
Operation
NV
SNVT_temp_p
Function
Using NV
Operation
Function
Using NV
Operation
Field
value
state
Total OnOff input
network variable : SNVT_switch, nviTotalOnOff
Total OnOff control
Operation
not used (set in 0 % usually)
0 = OFF
Total Temperature input
network variable : SNVT_switch, nviTotalTemp
Total Temperature control
Operation
18 ~ 30 °C
Temperature Unit input
network variable : SNVT_switch, nviTempUnit
Temperature Unit control
Temperature Unit display
network variable : SNVT_switch, nvoTempUnit
Temperature Unit monitor
Operation
not used (set in 0 % usually)
0 = Celcius
1 = Fahrenheit
1 = ON

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Plnwkb100

Inhaltsverzeichnis