7) Chilled Water Pump Interlock (Turbo Chiller)
Output
Valid Range
NV
SNVT_switch
8) Hot Water(Coolant) Pump Interlock (Turbo Chiller)
Output
Valid Range
NV
SNVT_switch
9) Model (Turbo Chiller)
Output
Valid Range
NV
SNVT_count
Function
Chilled Water Pump Interlock display
Using NV
network variable : SNVT_switch, nvoCWPumplock
Operation
Chilled Water Pump Interlock monitor
Field
value
state
Function
Hot Water(Coolant) Pump Interlock display
Using NV
network variable : SNVT_switch, nvoHWPumplock
Operation
Hot Water(Coolant) Pump Interlock monitor
Field
value
state
Function
Model display
Using NV
network variable : SNVT_count, nvoSetModel
Operation
Model monitor
Field
value
state
Operation
not used (set in 0 % usually)
0 = OFF
1 = ON
Operation
not used (set in 0 % usually)
0 = OFF
1 = ON
Operation
not used (set in 0 % usually)
0 = 2
1 = R134a
2 = R123