Uponor Supra Plus control unit
Operating voltage
230 VAC
Rated power
1500 W
Operating temperature range -20...+45C
Housing class
IP23
Indication by indicator light effective part
Adjustment range
- with thermostat
0...10°C
- with operation
10%...100%
Length of sensor cable
5 m
values of sensor
T°C
R kΩ
0
29
5
23
10
18
15
15
20
12
25
10
Figure 2
Figure 3
Figure 4
Remote control
a) Supply
Pe
L
cable
N
N
230 VAC
Pe
L
c) Heat
cable
b) Sensor
4
4
Product description
The Uponor Supra Plus control unit is an
electronic regulator developed to control the
Uponor Supra Plus water pipe, which is fi tted
with a self-adjusting heat cable. The control unit
has two different functions. You can select either
thermostat control equipped with a temperature
sensor, or an operation time clock function based
on a fi xed time period.
Installation instructions (Figure 2)
Fix the base of the housing to the wall with
screws (hole interval 60 mm, maximum screw
head diameter 6.5 mm). The tightness class of the
surface installation housing is IP23. The housing
can also be mounted on top of an instrument
box, in which case the tightness class is IP20. The
fi xing holes are dimensioned according to the
most generally used instrument boxes. On the
back cover of the housing, for installation on top
of an instrument box, an area with reduced thick-
ness has been provided, which can be pierced for
the lead-through of cables. Fix the cover of the
housing to the base part with M2.5 screws. If the
lead-through seals to be used are any other than
those supplied in the package, then they must be
approved for the cable thickness to be used and
for tightness class IP23. Install the sensor in the
Uponor Supra Plus pipe element, in the conduit
provided for it. The sensor is supplied ready-
installed inside the insulating sleeve. Lead the
insulating sleeve through the lead-through seal
and into the conduit of the pipe element, so that
it functions as a protector for the sensor cable.
If possible, the sensor should be installed at the
point that is the most susceptible to freezing. If
the sensor cannot be put at the coldest point,
then this must be taken into account in the
control unit settings or an operation time clock
must be used.
Connection (Figures 2 and 3)
Remove the adjusting wheel, detach the fi xing
screw and remove the cover part of the control
unit (Figure 2). Connect the 230 V AC supply
cable (Figure 3a), the sensor cable (Figure 3b),
the heat cable of the Supra (Figure 3c) and the
protective earth, to the incoming supply cable
and the protective fl ex of the heat cable. The
thickness of the connecting wires is determined
a
according to the size of the main fuse. 10A -> 3
b
x 1.5 mm
2
and 16A -> 3 x 2.5 mm
lations should be carried out in accordance with
c
the fi xed installation method. The control unit
also has a potential-free switch (230 VAC or SELV
d
voltage, max load 5A) for remote control, which is
activated in a fault situation. If necessary, punch
a hole in the top part of the device for the remote
e
monitoring cable, which must be laid according to
f
the requirements of the control voltage.
U P O N O R S U P R A P L U S C O N T R O L U N I T • M O U N T I N G I N S T R U C T I O N
Start-up and use (Figure 4)
Turn on the Uponor Supra Plus control unit
using the switch (f). When the control unit
is on, the green indicator light (e) above
the switch will go on. Select the function
alternative to be used. The selection is made
by setting the adjusting wheel of the control
unit to the desired adjustment range. The
left adjustment range (pos. 6-10) is for
the thermostat function, and the right one
(pos. 2-6) is for the operation time clock.
The adjustment ranges are limited by a
mechanical barrier. If you wish to change the
mode of operation, pull the adjusting wheel
outwards from the control unit and turn the
wheel to the desired adjustment range (the
mechanical barrier limiting the adjustment
ranges is at the 6 o'clock position).
The adjustment range for the thermostat
function of the Uponor Supra Plus control
unit is 0...10°C. If the adjusting wheel is set
to the 0 point of the adjustment range, then
the control unit will endeavour to keep the
temperature of the fl ow pipe at +0°C. The
temperature adjustment must nevertheless
be made according to the case, depending
on the location of the sensor and the envi-
ronment of use.
The adjustment range of the operation time
clock corresponds to a switching cycle of
30 minutes. In the maximum position, at
100 %, the heat cable is on throughout the
whole cycle. In the minimum position, at 10
%, the heat cable is on for 3 min. and off for
27 min. The cycle period should be selected
according to the case, depending on the
prevailing conditions. When the operation
time clock is being used for the thawing of a
frozen pipe, set the selector at 100 %. When
the heating load is in the switched-on state,
the red indicator light (c) above the adjusting
wheel will be on, showing that the cable is
being heated.
The control unit's fault diagnostics system
will detect any breaks or short circuits in
the sensor cable and whether the heating
cable is connected or not. The top LED (a)
2
. The instal-
indicates that there is no load in the cable,
and the bottom LED (b) indicates that the
sensor is faulty (this check is only made in
the thermostat mode). If a fault occurs in the
sensor, the thermostat operation changes
automatically to the operation time clock. In
this case, the device operates at a fi xed pulse
ratio of 50 %. In this fault situation, it is not
possible to adjust the operation time clock.
When the regulator is operating normally, a
faint clicking noise is heard when the heating
load goes on and off.