Herunterladen Inhalt Inhalt Diese Seite drucken

Connection Diagram; Interfaces - Honeywell mifare-Leser "Accentic" Anleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

22
Mounting and Connection Instructions mifare/DESFire EV1 reader "Accentic" with/without keypad
5.

Connection diagram

A plug has been soldered to the cable of the reader at the factory especially for test and
premounting sets. For the final installation, it usually has to be cut off.
5.1

Interfaces

The reader has the interfaces RS-485 and clock/data that can be used alternatively (Details see
Chapter 2. "Interfaces").
RS-485:
When started up, the reader automatically identifies the RS-485 interface.
The reader can be used remotely at a distance of max. 1200 m. We recommend
using a Cat 5 connecting cable.
If the reader is the last user on the RS-485 bus, a distributor with a 120 Ohm
terminating resistor (from A to B) must be installed in front of the reader.
For further information, refer to the description of the corresponding controller.
Clock/Data: To ensure reliable functioning, ensure that a possible extension of the 6 m connecting
cable does not exceed 200 m (Condition: no external interference voltage).
A JY(ST)Y 6x2x0.6 mm cable (DIN VDE 0815) can be used for extension purposes.
Attention:
Do not confuse the data
lines A and B, otherwise the
device will not function!
F
i
1
2
3
5
4
6
7
8
9
3
r
0
Reader with/without keypad
red
blue
yellow
white
black
violet
grey
red/blue
green
brown
grey/pink
pink
(free)
only mifare readers (026422 and 026423)
Shield
+U_b (9 V to 30 V DC)
0 V
A (D)
RS-485
B (D*)
Synchronization
Enable RS-485
CLK (D1)
DATA (D0)
LED green
LED yellow
LED red

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis