EA 21 mit montiertem Stellungs-
regler und Positionserfassung.
66

Mounting the positioner

1.
Disconnect the actuator from the supply
voltage.
2. Take the controller board out of the packaging and
check for damages.
Do not touch the board itself. Electrostatic
discharge can damage the components.
3. Place the board vertically on the back side of the base
board on plug X1. (see page 47)
Make sure that the board is inserted exac
tly in the guides at the side.
Setting the position signalization see Section 9.6
Connecting the positioner
For the positioner to receive the set value signal, connect
the terminals of the set value inputs 20 to 23 for the corre-
sponding values. (see table below) Cable cross-sectional
area max. 1.5mm
2.
Mind the configuration of the set value (see signal configu-
ration):
Terminal assignment Positioner 199 190 100:
20
SET value input current
21
SET value input voltage
22
-
23
SET value input ground
30
Position signalization signal
31
Position signalization ground