Herunterladen Inhalt Inhalt Diese Seite drucken

Mounting And Connecting Supplementary Kits; Heating Element - GF EA 21 Bedienungsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Wiring diagram
Heating element kit
LED on =
heating operation
4
46
7. Mounting and Connecting
Supplementary Kits

7.1 Heating Element

Description
Heating element
The heating element is mounted on the base board and is
connected electrically via a flat cable (X1). The temperature
is measured with a temperature sensor, which is mounted
on this element, and between approx. 0 - 5°C the heating
element is switched on.
Mounting the heating element (board)
1. Disconnect the actuator from the supply voltage.
2. Remove actuator cover.
3. Take the board out of its packaging and check for damages.
4. Screw the three distance bolts (1) into the assembly
bolts. Screw hand-tight.
2
5. Fasten the board (3) on the distance bolts with the sup-
plied screws (2).
3
6. Plug the flat cable into the X1 (4) connector.
1
7.
Put the cover back onto the actuator.
8. Reconnect to supply voltage.
The heating element may not heat at temperatures over
+ 5 °C, but in case it is switched on it might heat up to
10-15 °C.
Technical data
24 V=
Do not touch the board itself. Electrostatic
discharge can damage the components.
Code
199 190 086