6.3 Technical Specifications

Rated voltage
Rated voltage tolerance
Rated output @ 24V AC/DC
@ 100 – 230V AC
Electric impedance
Altitude over NN (UL/CSA)
Protection class
Duty cycle
Overload protection
Electrical connections
Nominal torque Mdn
Actuating angle
Control time
Peak torque
Ambient temperature
Allowable humidity
Pollution grade (4)
Overvoltage category (4)
Housing material
Position indication
Emergency manual override
Flange pattern (5)
(1) Overload protection of the motor is dimensio-
ned so that the motor and the power supply board
are protected. As soon as the load is in the torque
range, the actuator runs again.
EA21
100 – 230V, 50/60 Hz
24V = /24V, 50/60 Hz
+/- 10%
22 VA
32 VA
40 VA
40 VA
230V, 100kΩ
24V, 4.7kΩ
< 2000m
IP 65 per EN 60529 *(3) UL/CSA: indoors use
100% (6)
current/time-dependent (resetting) *(1)
temperature dependent
Connector plug 3 P+E per DIN EN 175301-803
Cable gland M20 x 1,5 according to ISO 724
10 Nm
max. 180°, set to 90°
5 s / 90° at Mdn
20Nm
-10° to + 50°C (2)
max. 90% relative humidity, non condensing
2
II
PP fibreglass reinforced, flame retardant,external stainless
steel screws, non-losable
optical, integrated
integrated
F05
(2) For temperatures below -10°C as well as
condensation, the heating element no. 198 190
086 should be built in.
(3) Protection rating IP 67 for use of cable glands
and vertical installation
EA31
40 VA
60 VA
50%
60 Nm
15 s / 90° at Mdn
120 Nm
-10° to + 50°C (2)
F07
(4) Per EN 61010-1
(5) Per ISO 5211
(6) Reduced Duty cycle for UL certification
EA42
35%
100 Nm
25 s / 90° at Mdn
250 Nm
F07
45