5
Both switches on ON
ON
- Error message
without stopping the
OFF
actuator
1
2
Both switches on OFF
ON
- Error message with
OFF
stopping the actuator
(delivery position)
1
2
58
Cycle time monitoring
Description
Technical data
Cycle time
monitoring
Cycle time monitoring monitors the duration of a pre-set
cycle time of the electric actuator. If the cycle exceeds the
pre-set time, a failure is reported (see error message, page
20). For the corresponding value please refer to the table
below (values are valid for 90° actuation).
Switch setting
Cycle time monitoring [s]
EA21
0
7
1
10
position
2
15
3
20
4
25
5
30
6
35
7
40
8
45
9
50

Cycle counter

Description
Technical data
Cycle counter
This function allows setting a desired number of cycles. As
soon as the number of cycles exceeds the set value, an error
is reported (see error message, page 20). With the help of
the DIP switch (8) on the monitoring print it can be preset, if
the actuator should keep moving in this case, or if it should
move to its security position and remain there. (refer to
section error message).
Code
199 190 082
EA31
10
15
Delivery
20
25
Delivery
position
30
35
40
45
55
70
Code
199 190 083
EA42
15
20
25
30
35
40
Delivery
position
50
60
70
85