6 Operation
Display
System message
EN
screen
A01
Safe door open
A02
Safe internal temperature
too high
A03
Filter monitoring
A04
Ambient temperature
too high/low
A05
Icing hazard
H
A06
PSA
pressure-operated
switch
A07
Evaporator coil
A08
Condensate warning
A09
Condenser fan
A10
Evaporator fan
A11
Compressor
A12
Condenser temperature
sensor
A13
Ambient temperature
sensor
A14
Icing temperature sensor
A15
Condensate warning
temperature sensor
A16
Internal temperature sensor Open or short-circuit
A17
Phase monitoring
A18
EPROM error
A19
LAN/Master-Slave
A20
Voltage drop
E0
Display message
OL
Overload
LH
Low heat
rSt
Reset
Tab. 5: Troubleshooting with the Comfort controller
36
Possible cause
Door open or door limit switch incorrectly
positioned
Cooling capacity inadequate/unit undersized.
Error as a consequence of messages A03 to
A17.
Filter mat soiled
Ambient temperature outside of admissible
operating range (+10°C to +60°C)
Operational display in case of icing hazard.
Evaporator coil fan may be mechanically
blocked, defective, or cold air outlet ob-
structed.
Ambient temperature too high
Condenser soiled
Filter mat soiled
Condenser fan defective
E-valve defective
H
PSA
pressure-operated switch defective
Lack of coolant; sensor in front of or behind
condenser defective
Condensate discharge kinked or blocked
Only in units with optional condensate
evaporation
Blocked or defective
Blocked or defective
Compressor overloaded
(internal winding protection)
Defective (check by measuring the winding
resistance)
Open or short-circuit
Open or short-circuit
Open or short-circuit
Open or short-circuit
For three-phase devices only:
Incorrect rotary field/phase absent
New board obstructed
Master and slave not connected
Error display not shown
Connection problem between the display
and the controller board
Cable defective; connection loose
Ambient parameters or heat loss outside of the applicable limits
Low heat loss inside the safe
Manual device reset required,
see section "6.1.8 Resetting the Comfort controller", page 37.
RITTAL Compact split cooling unit assembly and operating instructions
Measures to rectify the fault
Close door, position door limit switch correctly,
check connection if necessary
Check cooling capacity
Clean or replace;
reset the Comfort controller
Raise or lower the ambient temperature
(e.g. heat or ventilate the room)
Set the setpoint for the safe internal tempera-
ture to a higher value. Check the evaporator
fan; release or exchange if necessary.
Lower the ambient temperature;
reset the Comfort controller
Clean the condenser;
reset the Comfort controller
Clean or replace;
reset the Comfort controller
Replace;
reset the Comfort controller
Have the sensor repaired by a refrigeration
engineer; reset the Comfort controller
Have the switch replaced by a refrigeration
engineer; reset the Comfort controller
Have the sensor repaired by a refrigeration
engineer; reset the Comfort controller
Check condensate drainage;
repair any kinks or blockages in the hose
Check the evaporation unit, exchange if
necessary
Clear the blockage; replace if necessary
Clear the blockage; replace if necessary
No action required;
unit switches back on automatically
Exchange by refrigeration engineer
Replace
Replace
Replace
Replace
Replace
Exchange two phases
Software update needed (only following board
installation with more recent software): Enter
the programming level with Code 22;
press button 1 and confirm with "Set" until
"Acc" appears. Next, disconnect the unit from
the mains and reconnect.
Check setting and/or cable
Event is stored in the log file
Reset: Switch power supply off, then switch on
again after approx. 2 sec.
Exchange the boards