4.5.4 Door limit switch

– Each door limit switch must only be assigned to
one cooling unit.
– Several door limit switches may be connected in
parallel and operated on one cooling unit.
– The minimum cross-section for the connection
2
cable is 0.3 mm
for a cable length of 2 m.
– The line resistance to the door limit switch must not
exceed a maximum of 50 Ω.
– The door limit switch only supports a floating con-
nection; no external voltages.
– The contact of the door limit switch must be closed
when the door is open.
The safety extra-low voltage for the door limit switch
is provided by the internal power pack: Current
approx. 30 mA DC.
• Connect the door limit switch to terminals 1 and 2
of the connector.

4.5.5 Notes on the flicker standard

The flicker limits specified in standard EN 61 000-3-3
and -3-11 are adhered to, provided the supply im-
pedance is less than approx. 1.5 Ω.
Where necessary, the unit operator should measure
the connected impedance or consult the responsible
power supply company. If there is no way of influenc-
ing the supply impedance and sensitive installed
components (e.g. BUS) are subjected to interfer-
ence, a line reactor or starting-current limiting device
should be connected upstream of the cooling unit to
restrict the startup current of the cooling unit.
Evaporator coil
Condenser
Fig. 5:
Electrical wiring plan no. 1
RITTAL Compact split cooling unit assembly and operating instructions
Mains
21
S1
22
X2 X3
X1
L1 L2 L3
PE
1 2 3 4 5
3
8
PE
3
2
1
1 2 2 4 1 3
MS1
Serial
Power
5
K2
K1
D1 – 2
PE
D0 – A
A1
M1
M2
D1 – 3 D1 – 1 D1 – 4
4 3 2 1
4 3 2 1
1 2 3
4
1 2 3
1 3 5
95
F3 2
2 4 6
96
X10
L1
L2 L3
L1 L2 L3
PE
X20
1 2 3 4 5 6 7 8 9 10
X20
1 2 3 4 5 6 7 8 9 10
X10
L1L2 L3
PE
L1 L2 L3
PE
PE
4
U V W PE
U
V
F2
W
F3.1
M1
4 Assembly and connection

4.5.6 Potential equalisation

RITTAL recommends connecting a conductor with a
nominal cross-section of at least 6 mm
tial equalisation connection point in cooling units,
and incorporating it into the existing potential equal-
isation system.
According to the standard, the PE conductor in the
mains connection cable is not classified as an equi-
potential bonding conductor.

4.6 Carrying out the electrical installation

4.6.1 Installing the power supply

• Complete the electric installation using the electri-
cal circuit diagram shown on the rear of the exter-
nal unit and on the interior side of the maintenance
cover of the internal unit (see Fig. 1 on page 25,
legend on page 30).
• If you would like the system messages from the
cooling unit to be evaluated via the system mes-
sage relay, you should also connect a suitable
low-voltage cable to connection clamps 3 – 5.
2
B5
Level GRE
2
B1
NTC_I RED
2
NTC_E BLUE
B2
Term
M4 D1 – 5
1 2
3
1 2
2
2
4
PE
U V W PE
U V W PE
U V W PE
M
M
F5.1
PE
M
3~
3~
F5.2
M4.1
3~
M4.3
M4.2
A2
2
2
4
4
B4
B3
U V W PE
M
M
F4.1
F4.2
3~
3~
M2.1
M2.2
A2
2
to the poten-
U V W PE
F5.3
M
F5.4
3~
M4.4
EN
29