Ventilation and air extraction take place for
roughly 10 minutes. Then the fan is sw itched
off for a further 10 minutes so that the moist
room air can mix w ith the dry air brought in
from outside (passive time). After the w aiting
period has lapsed, the comparison of the
inside and outside humidity is repeated.
If the absolute humidity of the outside air is
found to be greater than that of the air inside
the room (aH
> aH
outer
exchanged. This prevents moist air from
flow ing in. The fan is only sw itched on again
once the climate conditions make
dehumidification possible.
Button 1
(Taster 1)
Button 2
(Taster 2)
LED 1
LED 2
Display
LED 1: On
LED 1: Blinking*
LED 1: Blinks
tw ice with long
pause
LED 1: Blinks
three times w ith
long pause
), air is not
inner
Reference value
determination
Manual ventilation
Operating mode
Dehumidification status
Function
Automatic operating mode
Manual ventilation
Frost protection
Protection against
insufficient humidity
3. Product information │ UK
LED 2:
On (in automatic
mode)
LED 2: Off
LED 2
Blinking*
* Sim ultaneous blinking:
Simultaneous blinking of LED 1 or LED 2
indicates an operating mode or function. If
both LEDs blink simultaneously, there is a
fault. See chapter Fault rectification.
Successful dehum idification –
Button 1 / Blinking LED 2:
In the case that the room humidity is reduced
3
by at least 0.2 g/m
, in comparison to the
reference value, the AKE 100 signals
successful dehumidification by LED 2
blinking. A reference value of 9 g/m
on-site. A new reference value can be set at
any time by pushing button 1 during ongoing
operation. Saving of the new reference value
is confirmed by the LED 2 blinking briefly.
Frost protection:
To prevent the room from cooling dow n,
the AKE 100 has a frost protection
function. This m eans that the fan
autom atically sw itches off at inside room
tem peratures of less than 5 °C.
Protection against insufficient hum idity:
For reasons of health protection and energy
efficiency, the AKE 100 offers a protection
against insufficient humidity function. This
protective function ensures the sw itching off
of the fan if a relative humidity of less than 30
% is reached.
Manual ventilation – Button 2: The AKE
100 sw itches the fan on and off automatically
and in a manner optimised to demand. When
off, the fan can be sw itched on manually w ith
button 2 and manual ventilation therefore
takes place. Manual operation is ended by
again pressing button 2 or automatically after
approximately 20 minutes.
Active time during
dehumidification
(Fan on)
Passive time during
dehumidification
(Fan off)
Successful
dehumidification achieved
(resettable w ith button 1)
3
is set
15