Troubleshooting - ABB CM-UFD.M21 Kurzanleitung

Netzeinspeiseüberwachungsrelais
Vorschau ausblenden Andere Handbücher für CM-UFD.M21:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Protective functions, default settings according to VDE-AR-N 4105 section 6.5.2
Overvoltage monitoring
10-minutes average value
Undervoltage monitoring
Overfrequency monitoring
Underfrequency monitoring

Troubleshooting

Error
8EEEE8
or
8-EEE8
appears in the display
8Err48
appears in the display
8Err58
appears in the display
8Err68
appears in the display
8Err78
appears in the
display + LED
of the
faulty output circuit is on
8Err88
appears in the display
8Err98
appears in the display
A time expires in the
display
Device cannot be
configured / only the
threshold values can be
configured
Implausible voltage
values
8Loc
8
appears in the display
8Code8
appears in the display
8stby8
appears in the display
Document no. 1SVC 510 810 M0000 A4
Terms acc. to VDE-AR-N 4105
8U,
8
Voltage increase protection
8UM
8
Voltage increase protection
8U_
8
Voltage decrease protection
8f,
8
Frequency increase protection
8f_
8
Frequency decrease protection
Cause
Measured voltage, frequency
or the vector shift is too large
or too small
Too high internal
measurement deviation of the
two measuring channels
Error internal regulation
Communication error internal
interface
Error feedback contacts
Hysteresis error:
overlapping of the release
points
Configuration error
If a OFF-delay 8dof
8
active, the time runs down in
the display (the shortest one
first)
Code lock / Sealing activated
Pr selected with N, but N not
connected
Sealing is active
Code lock is active
Standby mode, E1-E2 closed
Remedy
Consider the measuring range
Perform a reset 
interrupt the control supply voltage
for >5 s
Feedback contacts not connected
- set
8trel.8
Feedback contacts connected
- check the correct connection
- Adjust the turn-on time of the section
switch under
- Perform a reset  interrupt the control
supply voltage for >5 s
Upper threshold value must be higher than
the lower threshold value, check the
threshold values
Reset to factory settings, see "Program
setup"
is
Wait until the time is complete
(depending on the setting, several times
may elapse one after the other)
When having problems with the code lock
(Pin forgotten), the lock can be
deactivated and the pin can be reset to
504 , by pressing the button
/
off8
8Code8
while switching on the control supply
voltage
Select Pr without N or connect N
See 'Program setup'
See 'Code lock'
Check parameter
16 / 16
U>>
1.15 Un
100 ms
U>
1.1 Un
100 ms
U<
0.8 Un
100 ms
f>
51.5 Hz
100 ms
f<
47.5 Hz
100 ms
8 off8
8trel.8
until
is shown in the display,