Herunterladen Inhalt Inhalt Diese Seite drucken

Lenze EPM-H315 Betriebsanleitung Seite 58

L-force communication/hmi
Vorschau ausblenden Andere Handbücher für EPM-H315:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

4
Electrical installation
Wiring of the system bus (CAN)
Terminal assignment
(
Stop!
Connect a 120 W terminating resistor to the first and last bus device.
Terminal
1
2
3
4
5
For the use of the transmission cable, follow our recommendations:
Specification of the transmission cable
Total length
Cable type
Cable resistance
Capacitance per unit
length
58
Identification
Explanation
V−
GND
CAN−
LO
Shield
CAN+
HI
n.c.
£ 300 m
LIYCY 2 x 2 x 0.5 mm2
(paired with shielding)
£ 80 W/km
£ 130 nF/km
Reference potential
System bus LOW (data line)
Connect the shield of the system bus cable
System bus HIGH (data line)
Not connected
£ 1000 m
CYPIMF 2 x 2 x 0.5 mm
(paired with shielding)
£ 80 W/km
£ 60 nF/km
l
2
EDBPM−H315 DE/EN/FR 6.0