To set the Equalize Charge:
1) Remove all DC loads connected to the batteries.
2) Remove all battery vent caps.
3) Check the battery water level; it should be just over the top of
the plates (do not over fill). Use only distilled or demineralized
water for topping up.
4) Set the BATTERY TYPE SELECTOR switch to position "0" or
"1".
5) Reset the BATTERY TYPE SELECTOR switch to the
appropriate battery setting when all cells are fully charged (can
be verified with a hydrometer).
6) NEVER EQUALIZE Valve Regulated Lead Acid (VRLA)
batteries (commonly called Gel or AGM batteries)
4.3 Battery type selector
The battery type selector switch is a 10 position rotary switch used to set
the Controller for the proper absorption, float and equalize voltage levels.
These levels are selected depending on the type of batteries used. Refer
to the table below for the charge voltages in the various switch positions.
Consult the battery manufacturer for optimum battery charge settings.
Battery Type Selector
9