4.6
OPERATING PROGRAMME
Normal
1 st stage thermostat
2 nd stage thermostat
Motor
Ignition transformer
1 st stage valve
1 st stage flame
2 nd stage valve
2 nd stage valve
Lock-out lamp
Lock-out due to
failure to shut-down
A
Lockout is reported by the warning light belonging to the control box control and monitoring button
lighting (4, fig.1, page 2).
4.7 RE-CYCLE FUNCTION
The control box allows re-cycling, i.e. the complete repetition of the starting programme, for 3 attempts
maximum, in the event the flame goes out during operation.
4.8 POST-VENTILATION FUNCTION
Post-ventilation is a function that maintains air ventilation even after the burner is switched off. The burner
switches off when the limit thermostat (TL) opens, cutting off the fuel supply to the valves.
To use this function the reset button must be pressed when the limit thermostat is not switched over
(BURNER SWITCHED OFF).
Post-ventilation time can be set to a maximum of 6 minutes. Proceed as follows:
Press and hold the reset button for at least 5 seconds till the LED indicator changes to red.
®
Set the desired time pressing the button repeatedly: once = post-ventilation for 1 minute.
®
®
After 5 seconds the control box automatically shows the minutes set by the red LED flashing:
1 pulse = post-ventilation for 1 minute.
To reset this function, press and hold the button for at least 5 seconds at least, till the LED indicator
changes to red then release it without carrying out any operation, then wait for 20 seconds for the burner to
start.
If during post-ventilation there is a new request for heat, post-ventilation time is halted and a new operating
cycle starts when the limit thermostat (TL) switches over.
The control box leaves the factory with the following setting: 0 minutes = no post-ventilation.
4.9 CONTROL BOX RESET
To carry out the control box reset, proceed as follows:
Press the reset button for at least 1 second.
®
In the event of the burner not restarting it is necessary to check if the limit thermostat (TL) is closed.
3072
Lock-out due to
failure to light
5s
15s
8s
Lockout as a result of failed shutdown
A
during post-purging
15s
5s
10 GB
A
15s
8s
30s
D7090