Installation
5.3 Wall attachment of fixing plate and flush-mounted power
pack (accessory)
WARNING
Risk of electric shock!
As the flush-mounted power pack has to be connected to the
power supply of the building, there is a risk of electric shock.
The flush-mounted power pack must only be installed by a
qualified electrician.
CAUTION
Risk of fire due to overcharging of the batteries!
There is a risk of overcharging of the batteries if the "R-Tronic" is
equipped with batteries and is connected to the 230 V network via the
flush-mounted power pack.
The wireless thermostat must never be equipped with batteries
when using the flush-mounted power pack.
1. Switch off the current supply before installation of the flush-mounted
power pack.
2. Assemble the electrical connection between the flush-mounted power
pack and the 230 Volt connection in the flush socket.
3. Screw the fixing plate to the flush socket and switch on the current supply.
4. Insert the "R-Tronic" into the fixing plate from the top.
Fixing plate
2
Secondary cable
The flush-mounted power pack has to be installed
so that the primary cables (1) and the secondary
cable (2) do not touch each other. If necessary,
these cables are to be fixed, for instance with a
cable retainer in order to guarantee the physical
separation.
The "R-Tronic" is now ready for the "teach in" process (see paragraph
X
6.2).
Flush-mounted
Flush socket
power pack
1
Primary cables 230 V
10/24
"R-Tronic RT B" (ENOCEAN)
"R-Tronic RT B" (ENOCEAN)
Remove batteries!