4.2
Technical data
Radio frequency
Radio range within the building
Transmission interval
Operation mode
Protection
Protective system
Ambient temperature
Energy supply
Battery life span
Display
Measuring range T (°C)
Accuracy at +25 °C
Casing
Casing dimensions
Type plate:
"R-Tronic RT B" (ENOCEAN)
868.3 MHz
Depending on materials and interference sources
Winter mode 10 min.; Summer mode 30 min.
Type 1 (EN 60730-1)
IP20 (EN 60529)
III – Protective low voltage
+5 °C up to +50 °C
Battery type AA 1.5 V Mignon LR6,
alkaline (no rechargeable batteries); optional mains
operation
about 2 years (battery capacity > 2,600 mAh)
0 °C up to +50 °C
ABS (ASA), traffic white similar to RAL 9016
85 x 85 x 35 mm (W x H x D)
7/24
LCD
± 1 K