Herunterladen Inhalt Inhalt Diese Seite drucken

Tecsis EGS80X002001 Betriebsanleitung Seite 44

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Betriebsanleitung/Operating manual
EGS80X002001
6.5.2 Fault current
The following table shows what the current output is during a fault,
depending on the settings:
Setting
Up/Down
Hold
Max
Min
6.5.3 Fault current
Please note when entering Start value and End value:
• Both values are to be entered in the units, which were selected under
Units (section 6.2).
• Values between 0 mA and 20 mA can be entered, or between the
values of these limits converted into the selected units, using the
parameters Zero point and Conversion factor see section 6.3.2 The
difference between End value and Start value must be at least 1 % of the
End value (preset automatically by the Transmitter Power Supply).
44
0 mA ... 20mA
21,5 mA
with short-circuit
0 mA
with lead breakage
(not distinguishable
from Start value
measurement)
Last measured value before the fault
21,5 mA
0 mA
(not distinguishable
from
Start value
measurement)
BD_BE 987 b
4 mA ... 20 mA
4 mA ... 20mA
NE43
21,5 mA
22 mA
with short-circuit
with short-circuit
(not distinguishable from
End value overrange)
2,0 mA
0 mA
with lead
with lead breakage
breakage
(not distinguishable from
Start value measurement)
21,5 mA
22 mA
(not distinguishable from
End value overrange)
2,0 mA
0 mA
(not distinguishable from
Start value measurement)
www.tecsis.de