10 minutes of non-occupancy (no signal from presence detector).
Preset operating mode
Occupied is the preset operating mode. It can be set to Stand-by with
DIP-switch SW3. See table 3 above.
Occupancy detector
An occupancy detector is connected for local control of the operating
mode between Preset operating mode and Bypass.
Open window
Heating and cooling are disconnected.
Setpoint
Local setpoint displacement (+/-3°C) set with the knob on the front of
the controller.
In Occupied mode, the controller operates from a heating setpoint
(22°C), or a cooling setpoint (24°C) that can be changed locally using
the DIP switches and local setpoint displacement.
Switching between heating and cooling setpoints is done automatical-
ly in the controller depending on the heating and cooling requirement.
The controller's control setpoint is the same as the current setpoint
plus/minus the local setpoint displacement.
Frost protection
Independent of the operating mode, the heating control is forced on
when the room temperature drops below 8°C. Return to normal con-
trol occurs automatically when the room temperature exceeds 8°C.
Condensation detector
If there is condensation, the cooling control is blocked. Return to nor-
mal control occurs automatically when condensation ceases.
Indications
RC-T has an LED shaped like a thermometer on the front. A red
indication is shown when heating control is functional and a blue
indication when cooling control is active. No LED indication shows
that neither heating nor cooling control is active. A flashing red/blue
indication shows that a setting is incorrect.
Actuator exercise
All actuators are exercised. The exercise takes place at intervals of
23 hours. An opening signal is sent to the actuator for 120 s (the
actuator running time). Then a closing signal is sent for the same
length of time and the exercise is finished.
This product carries the CE mark.
For more information, see www.regincontrols.com.
Contact
AB Regin, Box 116, 428 22 Kållered, Sweden
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50
www.regin.se, info@regin.se
RC-T
INSTRUKTION
SV
REGIO RC-T
i
Läs denna instruktion innan produkten
monteras och ansluts
Rumsregulator med utgångar för två ventiler
med trepunktsställdon
RC-T är en rumsregulator i Regio Mini-serien avsedd att styra värme
och kyla i efterbehandlingssystem. Den har fyra digitala utgångar för
styrning av två ventiler med trepunktsställdon (öka-minska). Montage
sker direkt på vägg eller eldosa. Regulatorn har ej kommunikations-
anslutning.
Tekniska data
Matningsspänning
18...30 V AC, 50...60 Hz
Egenförbrukning
2,5 VA
Omgivningstemperatur
0...50°C
Omgivande luftfuktighet
Max 90% RH
Lagringstemperatur
-20...+70°C
Inbyggd temperaturgivare
Typ NTC, mätområde 0...50°C,
mätnoggrannhet +/-0,5°C vid 15...30°C
Gångtid, 3-punktsställdon
120 s
Ingångar och utgångar
Se inkopplingsbilder och tabell nedan
Anslutningsplintar
Av hisstyp för kabelarea max 2,1 mm
Skyddsklass
IP20
Material hölje
Polycarbonat, PC
Vikt
110 g
Mått
95 x 95 x 31 mm
Börvärdesratt
Lysdiod
Installation
Montera regulatorn på en plats med för rummet representativ tem-
peratur. Lämplig placering är ca 1,6 m över golvet, utan omgivande
hinder för luftcirkulation. Ta av ramen genom att trycka in låshaken i
nederkanten av kåpan med en skruvmejsel. Se figur 1.
2
3