1.6
RS485 Communication
According to the models, this meter can be without communication or equipped with
RS485 ModBus RTU / TCP or RS485 BACNET
1.6a
RS485 ModBus RTU / TCP Communication
Address number:
1...255
moves the cursor
increases/decreases the loaded value
confirms
Transmission speed:
4800 – 9600 – 19200 – 38400 bit/s
selects speed
confirms
Parity bit:
none – even – odd
selects parity
confirms
Waiting time before answer:
moves the cursor
increases/decreases the loaded value
confirms
07/16 10783322 WEB E cod.MFD4421SR
communication.
3...99ms
ModBus message word format:
selects format
confirms
1.6b
RS485 BACNET Communication
Address:
0...127
moves the cursor
increases/decreases the loaded value
confirms
Transmission speed:
9600 – 19200 – 38400 - 76800 bit/s
selects speed
confirms
Parity bit:
none – even – odd
selects parity
confirms
Nemo D4-Le
Rogowski
Big Endian – Little Endian – Swap
9