TECHNICAL CHARACTERISTICS

Voltage
Rated voltage Us
Operating voltage range
Rated frequency
Operating frequency range
Power consumption/dissipation
Current
Minimum current (Imin)
Transition current (Itr)
Reference current (Iref - Ib)
Max current (Imax)
Start current (Ist)
Burden (per phase)
Tariff command circuit
Rated voltage Uc
Operating voltage range
Rated frequency
Operating frequency range
Power consumption/dissipation
Accuracy
Active energy (IEC/EN 62053-21)
LED pulse
Number of pulses
Pulse length
Static outputs
Number of pulses
Pulse length programmable
External voltage
Maximum current
Ambient conditions
Mounting
Operating temperature
Storage temperature
Relative humidity
Maximum pollution degree
Overvoltage category
Altitude
Climatic sequence
Shock resistance
Vibration resistance
~
220 - 240V
L-N
~
380 - 415V
L-L
Device can operate with or without N
~
187 - 264V
L-N
~
323 - 456V
L-L
50/60Hz
45 - 66Hz
6VA / 1.5W
0.05A
0.25A
5A
6A
0.01A
≤ 0.3W
~
100 - 240V
~
85 - 264V
50/60Hz
45 - 66Hz
0.25VA / 0.18W
Class 1
10000 pulses / kWh
30ms
Programmable
0.1-1-10-100 pulses / kWh
100ms
~
10 - 30V
50mA
Indoor use only
-25 to +55°C
-25 to +70°C
<80 (IEC/EN 60068-2-70)
2
3
≤2000m
Z/ABDM (IEC/EN 60068-2-61)
15g (IEC/EN 60068-2-27)
0.7g (IEC/EN 60068-2-6)
Insulation
Rated insulation voltage Ui
Rated impulse withstand voltage Uimp
Power frequency withstand voltage
Supply / measurement connections and tariff
Type of terminal
Number of terminals
Conductor cross section (min... max)
Tightening torque
Current inputs and pulse outputs connections
Type of terminal
Number of terminals
Conductor cross section (min... max)
Tightening torque
Housing
Version
Mounting
Material
Degree of protection
Weight
Certifications and compliance
Comply with standards
To warrant protection requirements, the meter must be mounted in an IP51 enclosure class or better.
(IEC/EN 60529).
CLASS 1 LED PRODUCT
INVISIBLE LED RADIATION
950 nm, max 50 µW
EN 60825-1:1994+A1:2002+A2:2001
IEC 60825-1:1993+A1:1997+A2:2001
~
250V
6kV
4kV
Screw (fixed)
4 for Aux supply / measurement
2 for tariff input selection
2
0.2...4.0 mm
(24...12 AWG)
0.8Nm (7lbin)
Screw (fixed)
6 for CT connection;
4 for pulse outputs connection
2
0.2...2.5 mm
(24...12 AWG)
0.44 Nm (4 lbin)
4 module (DIN 43880)
35mm DIN rail (IEC/EN 60715)
or by screws using extractible clips
Polyamide RAL 7035
IP40 on front ∂
IP20 terminals
332g
IEC/EN 61010-1, EN 50470-3, UL508, CSA C22.2 n°14