Ensure that the specified protection grades are upheld.
To prevent loosening, if necessary use an additional hexagonal locknut or suitable thread
locking fluid.
Wiring
WARNING
Disconnect the device from the power source before starting any operations.
Ensure that the voltage is correct before beginning any maintenance or connections.
The device must be electrically installed and serviced by skilled persons.
Earth connection ferrule should be of a suitable material to avoid corrosion.
Use suitably color coded conductors or other means of identification. Earthing conductors
should be green and yellow.
Use only certified cable devices that matches the end application.
In each installation, main equipotential bonding conductors shall connect to the main
earthing terminal extraneous conductive-parts of that installation. Where supplementary
equipotential bonding is necessary, it shall connect together the exposed conductive-parts of
the device in the circuits concerned and extraneous-conductive-parts. The external bonding
cable shall be at least 4 mm
2
.
16