Connecting the control unit
Safety instructions
WARNING!
Protection.Class.I.device.
Danger.of.electric.shock!
•.
Securely.connect.the.protective.earth.(PE).
•.
Use.B.10.A.or.B.16.A.type.unit.as.circuit.breaker.
WARNING!
The.DALI.interface.is.insulated.by.a.basic.insulation.
Danger.of.electric.shock!
•.
Use.wires.that.can.handle.power.line.voltages.for.the.entire.DALI.wiring.
•.
Include.DALI.wiring,.with.a.5-core.cable.(e.g..NYM.5.x.1.5.mm²).if.necessary,.
together.with.the.mains.voltage.(L,.N,.PE).
•.
Do.not.connect.the.DALI.wiring.with.external.voltage,.especially.not.with.230.V.
mains.voltage..Any.potential.overvoltage.is.only.checked.when.starting.up.the.
DALI.Professional.
CAUTION!
Destruction.of.the.control.unit.and.other.devices.through.incorrect.mounting!
•.
Connect.relay.contacts.with.max..5.A.ohmic.load.
•.
Connect.an.interference.suppressed.contactor.in.between.for.higher.loads.
•.
Using.electronic.ballast.reduces.the.switching.load,.with.respect.to.ohmic.loads,.
at.the.same.wattage.
VI.2010
Installation