Kemper FK-5 PRO Betriebsanleitung Seite 119

Vorschau ausblenden Andere Handbücher für FK-5 PRO:

Werbung

8
Nr.
Error /
Fehlerbeschreibung
Warning
/ Info
Error
Water loss in tank
14
Error
Temperature
measurement out of
range
19
Error
Caution: Risk of frost
Take frost protection
measures
20
(< 2 °C)
Error
Caution: Temperature
high (> 55°C)
21
Error
Overflow at free drain!
22
Error
Battery missing
23
Error
Battery faulty
24
Error
Battery empty
25
Ursache
The level has dropped by approx.
i
100 mm in standby or device off mode.
Incorrect reading or defective
temperature sensor.
Temperature at sensor < 2°C.
Temperature at sensor > 55°C.
Overflow sensor triggered.
Sensor must remain closed for 2 seconds before
the fault is triggered.
No battery has been detected when starting
the controller.
Battery has been installed the wrong way
round or is defective.
Battery no longer has enough
power to close the servo drives.
1. Frequent closing of the servo drives due to
power cuts without sufficient battery charging time.
2. Battery faulty.
Lösung
1. Remove hood.
2. Visually inspect the device for leaks.
3. If the device is not leaking, call customer service.
Resistance measurement PT1000 sensor.
Replace if faulty.
Widerstandsmessung PT1000 Sensor.
Bei defekt tauschen.
Umgebungsbedingungen kontrollieren und
sicherstellen, dass Temperatur nicht weiter steigt.
Überlaufsensor kontrollieren, möglichen
i
Rückstau aus Kanal beachten.
Prüfen, ob Akku eingebaut ist.
Einbaurichtung des Akkus prüfen.
1. Dem Akku Zeit geben um aufgeladen zu werden.
2. Akku austauschen.
© www.kemper-group.com – K410036930001-00 / 12.2024 – 119 /120