Technical Data

Input
Nominal voltage U
:
N
Voltage range:
Nominal consumption:
Overvoltage protection:
Classification:
Test pulse duration:
Test pulse intervall:
Input resistance B1+, B2+
RK 6929.22:
RK 6929.16, RK 6929.22/100: ≥ 650 Ω
Input capacity:
Output
Contacts
RK 6929.16:
RK 6929.22:
Operate time:
Release time:
Contact type:
Switching voltage:
Thermal current I
:
th
Switching capacity
to AC 15:
NO contact:
NC contact:
To DC 13:
NO contact:
NC contact:
To DC 13:
NO contact:
NC contact:
Electrical life
at 6 A, AC 230 V cos ϕ = 1:
Max. operating frequency:
Short circuit strength
max. fuse rating:
Mechanical life:
General Data
Operating mode:
Temperature range:
Operation:
Storage:
Altitude,
Clearance and creepage distance
Rated impulse voltage /
pollution degree:
Contacts against all others:
Contacts to each others:
To IEC 61010-1:
EMC
Interference suppression:
Degree of protection
Housing:
Terminals:
Enclosure:
Vibration resistance:
Frequency / Amplitude:
Acceleration:
Climate resistance:
Terminal designation:
Wire connection:
Mounting:
Weight:
DC 24 V
The power supply unit must fulfit the
requirements of SELV / PELV
0.7 ... 1.15 U
N
< 1.0 W
Internal with MOV
Interface Typ C class 1 (ZVEI CB24I)
≤ 1 ms
≥ 50 ms
≥ 350 Ω
< 10 nF
1 NO contact,1 NC contact for
feedback circuit
2 NO contacts,1 NC contact for
feedback circuit
Max. 15 ms
Max. 15 ms
Relay, forcibly guided
Max. AC 250 V
Max. 6 A
(see quadratic total current limit curve)
3 A / AC 230 V
IEC/EN 60947-5-1
1 A / AC 230 V
IEC/EN 60947-5-1
2 A / DC 24 V
IEC/EN 60947-5-1
2 A / DC 24 V
IEC/EN 60947-5-1
4 A / DC 24 V at 0.1 Hz
4 A / DC 24 V at 0.1 Hz
≥ 1 x 10
switching cycles
5
1200 switching cycles / h
6 A gG / gL
IEC/EN 60947-5-1
40 x 10
switching cycles
6
Continuous operation
- 25 ... + 60 °C
(see quadratic total current limit curve)
At an altitude of > 2000 m the maximum
permissible temperature reduces by
0.5 °C / 100 m
- 40 ... + 85 °C
IEC 60664-1
≤ 2000 m
> 2000 m to ≤ 4000 m
6 kV / 2
4 kV / 2
6 kV / 2
4 kV / 2
≤ 2000 m
> 2000 m to ≤ 4000 m
Reinforced
Reinforced insulation
insulation
overvoltage category 2
overvoltage
or overvoltage category 3
category 3
with switching voltage
≤ 150 V
IEC/EN 61326-3-1
Limit value class B
EN 55011
IP 40
IEC/EN 60529
IP 20
IEC/EN 60529
Thermoplastic with VO behaviour
according to UL subject 94
IEC/EN 60068-2-6
10 ... 57 Hz, 0.075 mm constant
57 ... 150 Hz, 1 g constant
25 / 060 / 04
IEC/EN 60068-1
EN 50005
Captive slotted screw or
cage clamp terminals
DIN-rail
IEC/EN 60715
75 g
Technical Data
Dimensions
Width x height x depth
RK 6929 PC:
RK 6929 PS:

Standard Types

RK 6929.22PS/100 DC 24 V
Article number:
• Output:
• Nominal voltage U
:
N
• Width:
RK 6929.16PS DC 24 V
Artikelnummer:
• Output:
• Nominal voltage U
:
N
• Width:

Variants

RK 6929._ _ / _1_ and _2_:
For switching small loads of 10 mVA ... 12 VA or 10 mW ... 12 W in the
ranges 2 ... 60 V and 2 ... 300 mA.
The device is also suitable for switching the maximum switching current.
However, this will burn off the gold plating of the contacts, so that switching
of small loads is no longer possible afterwards.
RK 6929 ._ _ _ _ / _ _ 0 DC 24 V

Troubleshooting

Failure
LED "K1/K2" does not light up
LED "K1" does not light up
LED "K2" does not light up

Maintenance and repairs

- The device contains no parts that require maintenance.
- In case of failure, do not open the device but send it to manufacturer
for repair.
14
17.5 x 122 x 71 mm
17.5 x 107 x 71 mm
0069180
2 Schließer, 1 Öffner
DC 24 V
17.5 mm
0069176
1 Schließer, 1 Öffner
DC 24 V
17.5 mm
Nominal voltage
Contact material
0 = Standard
1 = Same as _0_ , but with Y1/Y2
with gold plating
for switching small loads
2 = All contacts with
gold plating
for switching small loads
Control
0 = Single channel with 1 LED
1 = Dual channel with 2 LED´s
Type of terminals
PC (plugin cageclamp):
Pluggable terminal blocks,
with cage clamp terminals
PS (plugin screw):
Pluggable terminal blocks,
with screw terminals
Contacts
Type
Potential cause
- Power supply not connected
- Power supply not connected
- Power supply not connected
RK 6929 / 14.07.23 en / 766A
Inhaltsverzeichnis
loading

Inhaltsverzeichnis