Evaluation Unit CES-A-.1B-01B-AS1
Technical data
Parameter
Value
Housing material
Plastic
Degree of protection
IP67
Ambient temperature
0 ... +50 °C
Weight
Approx. 0.4 kg
Operating voltage
DC 24 V +10% -15%
Power supply unit with safe
isolation
(EN IEC 61558-2-6:1998)
Current consumption, max.
600 mA
(via auxiliary power)
AS-Interface data acc. to
EA code: 7
AS-Interface specification 2.1
ID code: B
Operating voltage, AS-In-
DC 22.5 ...31.6 V
terface
Total current consumption,
100 mA
max.
Valid AS-Interface addresses
1 - 31
AS-Interface inputs
Acc. to AS-Interface Safety at
Work
CES input IN
(CES read head, socket M12,
AS-Interface bits D0 - D3
5-pin)
Dwell time min.
0.5 s
AS-Interface outputs
Current consumption max.
600 mA
Output OUT
(for CEM/CET solenoid, M12
AS-Interface bit D0
socket, 5-pin)
Times
Time-delay max. from state
180 ms
change
Risk time
180 ms
2)
Difference time (of the two
120 ms
dependent AS-Interface inputs)
Ready delay
3 s
Distances
min.
3)
Assured release distance s
-
ar
Cable lengths l = 0 ... 25 m
Operating distance s
10 mm
a0
Switching hysteresis
0.5 mm
Cable lengths l ≥ 25 ... 50 m
Operating distance s
8 mm
a0
Switching hysteresis
0.4 mm
Characteristics acc. to EN ISO 13849-1
Category
4
Performance Level (PL)
e
PFH
6.5 x 10
-9
D
2) Acc. to EN IEC 60947-5-3:2000
3) With evaluation unit CES-A-.1B-01B-AS1 in conjunction with read
head CES-A-LNA...AS1 or CES-A-LNA-SC and actuator CES-A-
BBA on surface mounting of the read head and the actuator. In
case of flush installation, the operating distances change as a
function of the installation depth and the guard material.
Normal operation
Safe code
closed
sequence
open
0000
X
0000
1)
Initial setup
open
0000
closed
0000
closed
0000
Status indication after switch-on
X
0000
1)
X
0000
1)
X
0000
1)
X
1)
0000
Feedback after teach-in operation
closed
0000
closed
0000
closed
0000
1) X = guard open or closed
Table 1: System states
typ.
max.
-
32 mm
Programming
17 mm
-
2 mm
-
14 mm
-
1.6 mm
-
2-channel dependent
Synchronization time
0.5 s
Table 2: Troubleshooting
With the read heads CES, CEM and CET, two processors each read the transponder in the actuator.
Fastening the actuator in the actuating range with small hysteresis can lead to even slight vibrations
causing the transponder to be read by only one processor (half-reading). This causes the yellow flashing
state to be indicated.
It is recommended to fasten the actuator in the actuating range so that the hysteresis is adequately large
(Fig. 3). If this cannot be implemented, the dual‑channel dependent with filtering module can be used in
the ASIMON software. More detailed information about this can be found in the ASIMON software manual,
which can be opened via the Help function of the ASIMON software.
State
on
on
off
Door closed
on
off
off
Door open
off
off
on
Error, device-internal failure or excessively high interference
flashing 4 Hz
off
off
Initial setup, ready for 1st teach-in operation
continuously
flashing at 1 Hz for
off
off
Teach-in operation
approx. 60 s
off
off
off
Teach-in operation complete, switch off device for setup
3 flashes once
off
off
One to five actuators have already been taught
6 actuators have already been taught
2 flashes once
off
off
2 memory locations still free
7 actuators have already been taught
1 flash once
off
off
1 memory location still free
8 actuators have already been taught
off
off
off
No memory location still free
1 flash continuously
off
on
9. Teach-in operation not possible
2 flashes contin-
off
on
Actuator already known, not allowed
uously
3 flashes contin-
Teach-in not successful
off
on
uously
Actuator was read for less than 60 s
State
Guard closed
Guard open, transponder only half-read
Half-sequence
Guard open, transponder only half-read
Guard open
Address 0 or communication disrupted
7
D0, D1
D2, D3
Monitor diagnostics
Code sequence
Green in ASIMON
00
Yellow flashing in ASI-
00
Half-sequence
Yellow flashing in ASI-
00
00
Red in ASIMON
Safe
Not safe
MON
Not safe
MON
Not safe
Gray