Herunterladen Diese Seite drucken

Emicon EMIBYTE WU Installation, Betrieb Und Wartung Seite 49

Präzisionsklimaschränke für kaltwasserbetrieb

Werbung

Emibyte WU - WUL
Unit regulation
Fan Regulation
Kp:
6.0
Ti:
120s
Unit regulation
°
DZ Fan:
0.0
C
Unit regulation
Comps./cooling coil
Kp:
8.0
Ti:
120s
Unit regulation
°
DZ Cooling:
0.0
Unit regulation
Supply air low limit
regulation
Kp:
6.0
Ti:
80s
Unit regulation
Limit max. dead zone
°
Fan:
0.5
C
°
Cooling:
0.5
C
Unit regulation
Humidification
Kp:
6.0
Ti:
80s
Unit regulation
Rehating heaters
Rehating:
2 STEPS
Setpoint offset:
Current set:
Step delay:
Unit regulation
Rehating PID heaters
Kp:
Ti:
Td:
Unit regulation
Temperature alarms
High return temp:
Setpoint:
Differential:
Low return temp:
Setpoint:
Differential:
Unit regulation
Temperature alarms
High supply temp:
Setpoint:
Differential:
Low supply temp:
Setpoint:
Differential:
Unit regulation
Humidity alarms
High return hum.:
Setpoint:
Differential:
Low return hum.:
Setpoint:
Differential:
MTEC.WU-WUL.DE-1 Betriebs und Wartungshandbuch WU-WUL Serie Deutsch
Präzisionsklimaschränke für kaltwasserbetrieb
Gb12
Gb17
Gb20
Gb21
C
Gb22
Gb23
Gb24
Gb32
°
5.0
C
Return
60s
Gb36
8.0
60s
0s
Gb40
°
30.0
C
°
1.0
C
°
5.0
C
°
1.0
C
Gb44
°
30.0
C
°
1.0
C
°
5.0
C
°
1.0
C
Gb46
95.0%
5.0%
5.0%
5.0%
49