Anhang
DiagCode
Fehlername (FB)
0x5823
ASi_HW_CONFIG_SLAVE_TEACH_ERROR_B_CHANNE
L_OPEN
Errorcode received from AS-i-Control
0x5824
ASi_HW_CONFIG_SLAVE_ERROR_CODESEQUENCE_I
NVALID
Errorcode received from AS-i-Control
0x5825
ASi_HW_CONFIG_SLAVE_TEACH_ERROR_CODESEQ
UENCE_DOUBLY
Errorcode received from AS-i-Control
0x5826
ASi_HW_CONFIG_SLAVE_TEACH_ERROR_CODESEQ
UENCE_RULES
Errorcode received from AS-i-Control
0x5827
ASi_HW_CONFIG_SLAVE_TEACH_ERROR_NO_CODE
SEQUENCE
Errorcode received from AS-i-Control
0x5830
ASi_HW_GLOBAL_COM_MISSING_BUS_CYCLE_EVEN
T
Errorcode received from AS-i-Control
0x5831
ASi_HW_GLOBAL_COM_ADDRESS SEQUENCE
ERROR
Errorcode received from AS-i-Control
0x5832
ASi_HW_GLOBAL_COM_FAILURE_TO_LESS_SLAVES
Errorcode received from AS-i-Control
0x5840
ASi_HW_ERROR_STATE_INIT
AS-i Slave fehlt
Fehler-Codes: Sichere AS-i Slaves
Fehlerbeschreibung
Fehlercode von AS-i Control-Slave empfangen
Fehlercode von AS-i Control-Slave empfangen
2 Slaves mit gleicher Codefolge im AS-i Netz
Fehler 0x5825 und 0x5826 können gleichzeitig
auftreten
Fehler beim Einlernen der Codefolge
Fehler 0x5825 und 0x5826 können gleichzeitig
auftreten
Fehler beim Einlernen der Codefolge
Am Steuerungs-FB wird dieser Fehler durch
Fehler 0x5840 überdeckt.
Alle Busfehler können lokale Fehler überdecken.
Alle Busfehler können lokale Fehler überdecken.
Zu wenige AS-i Slaves am Bus
kein AS-i Slave am Bus
Alle Busfehler können lokale Fehler überdecken.
Dieser Fehler kann von Fehler 0x5820
überdeckt werden.