STIEBEL ELTRON SBP 100 Plus Installation Seite 11

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
2.1.4 Signal words
Signal
Meaning
word
DANGER
Failure to observe this information will result in death or
serious injury
WARNING Failure to observe this information may result in death or
serious injury
CAUTION
Failure to observe this information may result in moderate
or minor injury
NOTICE
Failure to observe this information may result in property
damage, consequential losses or environmental damage
2.2
Intended use
The appliance is intended for the seasonal storage (around
5 months at a room temperature of 24 °C and relative humidity
of 40 %) of heating water cooled to +7 °C. Constant cooling op-
eration with heating water below +11 °C is not permissible.
The appliance extends the runtime of the heat generator and
bridges blocking times. The appliance enables hydraulic separa-
tion between the heat pump circuit and heating circuit flows.
The appliance is intended for domestic use. It can be used safely
by untrained persons. The appliance can also be used in non-
domestic environments, e.g. in small businesses, as long as it is
used in the same way.
Observation of these instructions and of instructions for any ac-
cessories used is also part of the intended use of this appliance.
2.3
Foreseeable misuse
Any other use beyond that described shall be deemed to be out-
side the intended use.
Using the appliance for heating fluids other than water or for
water supplemented with chemicals, such as  brine, is also
deemed inappropriate.
2.4
Safety instructions
– Unsuitable spare parts and accessories may jeopardise user
and appliance safety. Always use original spare parts and
original accessories.
3
Appliance description
The appliance extends the runtime of the heat generator and
bridges blocking times. The appliance enables hydraulic separa-
tion between the heat pump circuit and heating circuit flows.
The appliance is equipped with complete thermal insulation to
protect against the formation of condensate.
4
Transportation (qualified contract-
ors)
u Protect the appliance against heavy impact during trans-
port.
5
Installation (qualified contractors)
5.1
Installation site
The installation site must fulfil the following requirements:
– Free from the risk of frost
– Dry
The substrate on which the appliance is to be installed must
meet the following conditions:
www.stiebel-eltron.com
Appliance description
– Horizontal
– Fixed
– Permanent
– Sufficient load bearing capacity (for weight of the appliance,
see chapter Data table [} 13] ).
u To reduce line losses, keep the distance short between the
appliance and the heat pump.
u Observe the required room height (for height of the appli-
ance, see chapter Data table [} 13] ).
5.1.1 Minimum clearances
≥100
≥500
D0000111096
The minimum side clearances can be swapped between left and
right.
u Maintain the minimum clearances in order to ensure
trouble-free operation of the appliance and to allow enough
space for maintenance work.
5.2
Siting the appliance
u Lift the appliance out of the packaging.
u Position the appliance in the final installation site.
u Observe chapter Minimum clearances [} 11] .
u Use the adjustable feet to compensate for any unevenness
in the floor.
5.3
Heating water connection
u NOTICE: Foreign bodies, such as welding pearls, rust or
sealing material, can impair the operational reliability of
the appliance. Flush the pipework thoroughly before con-
necting the appliance.
u Install the pipes carrying heating water (see chapter Dimen-
sions and connections [} 13] ).
u Connect the hydraulic connections with flat gaskets.
Other connections
u Close off the connection "Do not use" (i31) (see chapter Di-
mensions and connections [} 13] ).
≥500
≥100
SBP 100 Plus |
11