Herunterladen Diese Seite drucken

Valpes VT1500 Installations- Und Bedienungsanleitung Seite 20

Actionneur électrique

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Technical data
Location
Materials
Sealing
Environment
Operating temperature
Operating altitude
Hygrometry
Pollution degree
Weight
Mechanical data
Nominal torque
Maximum torque
Operating time (90°)
Angular range
Duty cycle
Drive ISO5211
Manual control
Electrical data
Voltages
1)
Rated current
Overvoltage category
2)
Power
Torque limiter
Number of feedback switches
Limit switches voltage
Limit switches current
Anticondensation heaters
1)
The actuator tolerates voltage fluctuation of the electrical grid up to ± 10 % of its nominal system operating voltage
2)
The actuator tolerates temporary overvoltage of the electrical grid
20
VT1500
Housing: Aluminium + EPOXY paint / cover: PA6 UL 94 V-0 or Aluminium + EPOXY paint
Drive : Steel + Zn treatment / Axles and screws : Stainless steel
Both inside and outside (wet environments possible)
maximum relative humidity 80% for temperatures up to 31°C decreasing linearly to 50% rela-
Applicable POLLUTION DEGREE of the intended environment is 2
1200Nm
1500Nm
113s
F12/F14/F16 (depth F12 : 20mm / F14 : 25mm / F16 : 30mm)
Secured hand wheel without clutching system
230 V AC (50/60 Hz) • 3-phase 400 V (50 Hz)
400 V: 0,45 A (cos  = 0,8) • 230 V: 1,3 A (cos  = 0,8)
Max. 5 A (resistive), 0.5 A (motor), 0.125 A (capacitive loads)
IP68
-20°C to +70°C
Up to 2000m
tive humidity at 40°C
(in most cases).
54kg
90° (180°-270° on request)
50%
Star 36 (depth 41mm)
250W
Mechanical
2 (4 on request)
12 to 250 V AC and 4 to 24 V DC
Min. 100 mA
10W
DSBA3004 • Rév. 12/06/2023
ENGLISH
UK
VT2400
2000Nm
2400Nm
113s

Werbung

loading

Diese Anleitung auch für:

Vt2400