BNI EIP-508- _ 05-Z015- _ _ _
Network interface
5
Installation and connection (continued)
5.2.2
EtherNet/IP interface
Fig.5-2:
Top view of M12 socket, D-coded
Pin
Signal
Description
1
Tx+
Transmit Data +
2
Rx+
Receive Data +
3
Tx−
Transmit Data −
4
Rx−
Receive Data −
Tab. 5-2:
Pin assignment
5.2.3
I/O-Port
Fig.5-3:
Top view of M12 socket
Pin
Signal
1
US
+24 V, 2 A
2
I/O
Input / Output (2 A)
3
GND
Electrical ground 0 V
4
I/O, C/Q
Input / Output (2 A) / IO-Link
5
n. a.
Not available
Tab. 5-3:
Pin assignment
For the digital sensor inputs, see the directive on
inputs EN 61131-2, type 3.
Unused ports must be covered with caps to
ensure IP67 protection.
The IO-Link output is fed from the sensor supply.
10
english
Description
5.2.4
Grounding
To counteract EMC interference, the functional earth
connection must be used.
► Connect the earth terminal to the functional earth (FE)
of the machine.
The FE connection between the housing and
the machine must have a low impedance and
be as short as possible.
► Use the grounding strap included in the
scope of delivery.
Fig.5-4:
Ground connection
5.3
Cable routing
Cable length
The Ethernet cable may be max. 100 meters long.
The IO-Link single-ended cordset may be max. 20 meters
long.