BNI EIP-508- _ 05-Z015- _ _ _
Network interface
5
Installation and connection
5.1
Installation
For dimensions, see Fig.4-1 on page 7.
► Fasten the module with 2 M6 screws and a maximum
tightening torque of 3 Nm using the mounting holes
(see Fig.4-2 on page 7).
5.2
Electrical connection
Requirements for complying with the protection
classes:
For IP67, all plugs and caps must be properly connected
and the tightening torque of 0.6 Nm must be observed
(see data sheets of connectors and caps).
5.2.1
Power supply
NOTICE
Unwanted voltage dips
Non-separated electric circuits of the power supplies for
sensor and actuator can lead to unwanted voltage dips
of the sensor supply when switching actuators.
► Fuse the power supplies for sensors and actuators
separately.
► Make sure that the power supply of the device is
sufficiently dimensioned to cover start-up and peak
currents and design the fuse protection concept
accordingly.
– Establish power supply of sensor/bus and
actuator via a separate power source if possible.
– The total current for the sensor and actuator
supply must not exceed 9 A each.
– For UL: Observe cable requirements and power
supply requirements (see chapter 8.7.2 on
page 14)!
www.balluff.com
7/8" connector
Fig.5-1:
Top view of 7/8" plug (left) and socket (right)
Pin
Signal
Description
1
UA
Actuator supply +24 V
2
US
Module/sensor supply +24 V
3
GND
Common ground
4
Tab. 5-1:
Pin assignment
7/8" socket
english
9