Salda RIS 400HW 3.0 Technische Daten Seite 16

Werbung

RIS HW 3.0
1
2
3
X16
1 2 3 4 5 6 7 8 9 10
X16.1
2
3
1
X16.2
Y1 Y2 G
M5
24VAC, 3-position
Y1 - OPEN (24VAC)
Y2 - CLOSE (24VAC)
G - System potential 24VAC
Water cooler
valve actuator
carrier temperature sensor.
1 2 3 4 5 6 7 8 9 10
X16
1
2
3
4
X16.1
1
2
3
X16.2
Y1
Y2
G
M5
24VAC, 3-position
Y1 - OPEN (24VAC)
Y2 - CLOSE (24VAC)
G - System potential 24VAC
Water cooler
Boost
valve actuator
1
2 3 4 5 6 7 8 9 10
X16
1
2
3
4
X16.1
2
3
X16.2
1
Y1
Y2
G
M5
24VAC, 3-position
Y1 - OPEN (24VAC)
Y2 - CLOSE (24VAC)
G - System potential 24VAC
Water cooler
Boost
valve actuator
Įrenginio paleidimo ir derinimo darbus, iki
perdavimo vartotojui, turi atlikti tik atitinkamai
kvalifi kuotas ir apmokytas personalas. Norint,
kad vėdinimo įrenginio automatinio valdymo sis-
tema veiktų tinkamai, reikia ją tinkamai suderinti.
Taip pat matavimo, vykdymo įtaisus sumontuoti
pagal pateiktas rekomendacijas.
Temperatūriniai jutikliai, oro kokybės
keitikliai. Tiekiamo oro temperatūros jutiklius ir
oro kokybės keitiklius (jei naudojami papildomai)
reikia sumontuoti kuo toliau nuo vėdinimo
16
4
5
6
7
8
9
10
4
5
6
7
8
X16.3
X16.4
9
10
1
P
3
AHU status
DX Cooling
Start/Stop
Boost
AHU stop
5
6
7
8
9
10
4
5
6
7
8
X16.4
9 10
X16.3
1
P
3
Jumper
AHU status
DX Cooling
Start/Stop
AHU stop
5
6
7
8
9
10
4
5
6
7
8
X16.4
9 10
X16.3
1
P
3
Jumper
AHU status
DX Cooling
Start/Stop
AHU stop
Пусковые и наладочные работы, до передачи
устройства потребителю, должен выполнять
только обладающий соответствующей
квалификацией и обученный персонал.
Чтобы система автоматического управления
вентиляционным агрегатом работала
надлежащим образом, ее необходимо
наладить. Также необходимо в соответствии
с п р и в е д е н н ы м и р е к о м е н д а ц и я м и
смонтировать измерительные, командные
устройства.
RIS 1000HW 3.0
11 12 13 14 15 16 17
11
12
13
14
15
16
17
15
16
17
11 12
13 14
X16.4
NC
N
FA
N
L
L
M2
Jumper
230V AC
ON/OFF
Fire alarm
Supply air
AHU work
input
damper actuator
RIS 1500HW 3.0
11
12
13
14
15
16
17
11 12 13 14 15 16 17 18 19 20 21 22
11
12
13
14
15
16
17
X16.4
NC
N
FA
N
L
L
M2
Jumper
ON/OFF
Fire alarm
Supply air
AHU work
input
damper actuator
RIS 1900HW 3.0
11
12
13
14
15
16
17
11 12 13 14 15 16 17 18 19 20 21 22
11
12
13
14
15
16
17
X16.4
NC
N
FA
N
L
M2
Jumper
230V AC
ON/OFF
Fire alarm
Supply air
AHU work
input
damper actuator
Before commissioning, device launching and
adjustment works must be done only by qualifi ed
and trained personnel. Automatic control system
of the ventilation unit must be properly adjusted
to work adequately. Also, install measuring
and operating devices in line with the provided
guidelines.
Air temperature sensors and air quality
converters. Supply air temperature sensors and
air quality converters (if additionally used) must
be mounted as far as possible from the ventila-
18 19 20 21 22
23
24
18
19
20
21
22
23 24 25 26 27 28
X16.5
18
19
20
21 22
X16.7
23
X16.6
N
L
PE
TJ
N L L
M3
230V AC
1f, 230V AC
ON/OFF
NTC
Extract air
Supply air
Water heater
damper actuator
temp.sensor
circulation pump
18
19
20
21
22
23 24 25
23
X16.5
18
19
20
21
22
X16.7
X16.6
N
L
TJ
N
L
L
M3
1f, 230V AC
ON/OFF
Extract air
Supply air
Water heater
temp.sensor
circulation pump
damper actuator
18
19
20
21
22
23 24 25
23
X16.5
18
19
20
21
22
X16.7
X16.6
N
L
TJ
L
N
L
L
M3
230V AC
ON/OFF
NTC
Extract air
Supply air
Water heater
damper actuator
temp.sensor
circulation pump
Anlass- und Einstellungsarbeiten der Anlage
müssen bis zur Übergabe an den Benutzer nur
durch entsprechend qualifi zierte und geschulte
Fachkräfte ausgeführt werden. Falls man wün-
scht, dass das automatische Steuersystem von
der Lüftungsanlage richtig funktioniert, muss sie
entsprechend eingestellt werden. Mess- und
Servogeräte müssen laut vorgelegten Empfeh-
lungen montiert werden.
Temperaturfühler, Luftqualitätswandler:
Temperaturfühler der Zuluft und Luftqualität-
25
26
27
28
24
25
26
27
28
X16.8
N
0
Y
G
L
M6
M4
24VDC, 0-10VDC
0 - GND,
Y - 0-10V,
G - 24VDC.
Water heater
valve actuator
26
27 28
24
25
26
27
28
23
24
25
26
27
28
X16.8
N
0
Y
G
L
PE
M6
24VDC, 0-10VDC
M4
0 - GND,
Y - 0-10V,
G - 24VDC.
Water heater
valve actuator
26
27 28
24
25
26
27
28
23
24
25
26
27
28
X16.8
N
0
Y
L
G
PE
M6
24VDC, 0-10VDC
M4
0 - GND,
Y - 0-10V,
1f, 230V AC
G - 24VDC.
Water heater
valve actuator