Alarm 4 address 0/1
Alarm 5 address 0/1
Alarm 6 address 0/1
Alarm 7 address 0/1
Alarm 8 address 0/1
Alarm 9 address 0/1
Alarm 10 address 0/1
To save confi guration parameters, write 22 to the register 49, then settings are saved to EEPROM
memory, controller reloads.
Alarms
Al
ECO automation ala
Indication
Meaning (see device technical manual for alarm description)
Heat exchanger antifreeze protection
A.01
A.02
External protection activated
A.03
Return water critical temperature
A.04
"P-mA" output fault
A.05
Low voltage
A.06
Extracted air sensor fault
A.07
Supply air sensor fault
A.08
Return water temperature sensor fault
A.09
Ambient air temperature sensor fault
PRV automation ala
Indication
Meaning (see device technical manual for alarm description)
A.01
Heat exchanger antifreeze protection
A.02
Fire protection
A.03
Clogged fi lters
A.04
Fan fault
A.05
Low voltage
A.06
DTJ(100) temperature sensor alarm fault
A.07
Exhaust air sensor fault
A.08
Supply air sensor fault
A.09
DTJ(100) humidity sensor fault
A.10
Return water temperature sensor fault
A.11
Ambient air temperature sensor fault
36
alarms
alarms
Coil
0x04
Coil
0x05
Coil
0x06
Coil
0x07
Coil
0x08
Coil
0x09
Coil
0x0A
www.salda.lt
4
5
6
7
8
9
10