Defrost type, cycle inversion (hot gas) or
d1
with heater elements
dPo
Defrost at Power On
dSE
Smart defrost
Smart defrost Setpoint (if dSE=1)
The counting of the time between the defrost is
dSt
incremented only if the compressor is ON and the
evaporator temperature is less than dSt.
dFd
Display viewing during Defrost
Net address for connection to TeleNET
Ad
supervision system or Modbus
SEr
RS-485 communication protocol
Bdr
Modbus baudrate
Prt
Modbus parity check
Minimum
and
Ald
signalling and alarm display delay
Minimum
time
C1
subsequent
compressor.
CAL
Cold room sensor value correction
Duration of compressor ON time in the
case of faulty ambient probe (emergency
mode). If CE1=0 the emergency mode in the
CE1
presence of error E0 remains disabled, the
compressor remains off and defrosting is
prevented in order to conserve the remaining
cold.
Duration of compressor OFF time in the
CE2
case of faulty ambient probe (emergency
mode).
Compressor safety time for door switch:
when the door is opened the evaporator fans
doC
shut down and the compressor will continue
working for time doC, after which it will shut
down.
Compressor
opening: when the door is opened and after
tdo time, it's setted back the normal
functioning giving door open alarm (Ed)
tdo
If the door switch is closed and the light
stays on for a longer time than tdo light cell
alarm is signaled (E9).
With tdo=0 the parameter is disabled.
FAN shutdown TEMPERATURE
The fans will stop if the temperature value
Fst
read by the evaporator sensor is higher
than this value.
Fd
Fst differential
LSE
Minimum value attributable to setpoint.
HSE
Maximum value attributable to setpoint.
ECP202 BASE – Parameters Abstract
Pag. 4
maximum
temperature
between
shutdown
switching
on
of
restart
time
after
0 = heating element
1 = hot gas
2 = heater with temperature control
0 = disabled
1 = defrost at power-on (if possible)
0 = disabled
1 = enabled
-30 ÷ 30 °C
0 = current temperature
1 = temperature at the start of the defrost
2 = "DEF"
0 ÷ 31 (with SEr=0)
1 ÷ 247 (with SEr=1)
0 = TeleNET protocol
1 = Modbus-RTU protocol
0 = 300 baud
3 = 2400 baud
1 = 600 baud
4 = 4800 baud
2 = 1200 baud
5 = 9600 baud
0 = none
|
0 ÷ 240 min
and
the
0 ÷ 15 min
-10,0 ÷ +10,0 °C
0 ÷ 240 min
0 = disabled
5 ÷ 240 min
door
0 ÷ 240 min
0 = disabled
-45 ÷ +99 °C
1 ÷ +10 °C
-45 ÷ (HSE-1) °C
(LSE+1) ÷ +99°C
6 = 14400 baud
7 = 19200 baud
8 = 38400 baud
1 = even
|
2 = odd
0 ÷ 5 min
Rev. 01-21
0
0
0
1 °C
1
0
0
5
0
120 min
0 min
0,0 °C
0 min
5 min
0 min
0 min
+99 °C
2 °C
-45 °C
+99 °C