Herunterladen Inhalt Inhalt Diese Seite drucken

Application; Specifications - Honeywell VC Serie Einbauanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

1. Application

The VC series 2-position hydronic valves are used in
domestic and small commercial applications to control
the flow of hot and/or cold water or glycol solution to
50% concentration. They consist of an actuator, valve
and a replaceable cartrige assembly.
These 3-Way valves are designed for ON-OFF control
and can be piped for either diverting or mixing valve

2. Specifications

The following specifications are nominal and conform to generally accepted industry standards. Honeywell is not
responsible for damages resulting from misapplication or misuse of its product.
Voltage
Power Consumption
Maximum duty Cycle
End switch rating
Nominal timing
Electrical termination
Operating ambient temperature 0...65°C
Shipping & storage temperature -40...+65°C
Atmosphere
Min. & max. fluid temperatures
Operating pressure differential
Pressure rating
Valve materials
Insulation class
Protection class
Approval
C
D
98
136
94
130
94
130
94
136
94
136
Fig. 1: Dimensions (mm)
MU1H-2806GE23 R0107
GB
applications for domestic hot water service, in central
heating and/or cooling systems; or for individual room
temperature control (fan coil, radiator or convector
applications).
Depending on the model selected, they can be cont-
rolled by either a low or line voltage SPST
SPDT
a chronotherm or other suitable two-position controller.
230V 50-60Hz, standard models. 24V 50-60Hz models are available on
request
6 Watts Max. at nominal Voltage (during valve position change).
Use 24 V class 2 transformer. Provide 6 VA for transformer and connection
wire size.
15 %
2.2 A inductive from 5 to 110 Vac,
1.0 A inductive above 110 to 277 Vac.
Min. DC switching capability: 5 mA @ 24 Vdc
Valve opens in 7 seconds ≅ 50 Hz (20% faster ≅ 60 Hz)
With integral 1 meter leadwire cable or with Molex™ connector
non-corrosive, non-explosive
1...95°C
Max. - 4 bar (400 kPa)
Static - 20 bar (2000 kPa)
Burst - 100 bar
Body of bronze; cartridge of Ryton™ (polyphenylene sulphide) & Noryl™
(polyphenylene oxide); O-ring seals of EPDM rubber; stainless steel stem
Double insulation
IP40
CE
4
controller, such as a room thermostat,
Open
B-AB
Port A normally closed without actuator
Fig. 2: Flow direction
or
Open
A-AB
Honeywell GmbH

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Vc6613mp6000Vc6013mh6000u

Inhaltsverzeichnis