5.3 Monitored LED module - BR 50-LED-M
The function-monitored LED module for the Intense BR 50 signal tower can be used easily in combination with
other function modules for safety-relevant applications, for example. The diagnosis channel of the module (alarm
contact) can be incorporated here into a higher-level control system as a feedback signal.
A maximum of 3 modules can be used.
Nominal voltage
Functional area
Nominal current
Alarm output
Monitored module top:
5+/L NC
(not connected)
4+/L NC
(not connected)
3+/L Alarm contact 2
2+/L Alarm contact 1
1+/L 24V DC
-/N
0V
Monitored module bottom:
5+/L Alarm contact 2
4+/L Alarm contact 1
3+/L NC
(not connected)
2+/L NC
(not connected)
1+/L 24V DC
-/N
0V
*
Monitored module
top and bottom:
(max. 2)
06/2023
Operating Manual Intense Signal Tower BR 50
*
24 V DC
21.6 V – 26.4 V DC
35 mA
Max. 230 V AC/DC / 80 mA R
closed in error-free operation
5+/L NC
4+/L Alarm contact 2
3+/L Alarm contact 1
2+/L 24V DC 2nd stage
1+/L 24V DC 1st stage
-/N
0V
5+/L Alarm contact 2
4+/L Alarm contact 1
3+/L NC
2+/L 24V DC 2nd stage
1+/L 24V DC 1st stage
-/N
0V
5+/L
Alarm contact 2, Module 1
4+/L
Alarm contact 1, common alarm contact 1
3+/L
Alarm contact 2, Module 2
2+/L
24V DC 2nd stage
1+/L
24V DC 1st stage
-/N
0V
Page 6 / 13
35 Ohm
ON max
(not connected)
(not connected)
5+/L
Alarm contact 2
4+/L
Alarm contact 1
3+/L
24V DC 3rd stage
2+/L
24V DC 2nd stage
1+/L
24V DC 1st stage
-/N
0V
5+/L Alarm contact 2
4+/L Alarm contact 1
3+/L 24V DC 3rd stage
2+/L 24V DC 2nd stage
1+/L 24V DC 1st stage
-/N
0V
Alarm contact
Module 2
Alarm contact
Module 1
086200021