Option 30 - Set upper limit of temperature range
GB
This allows the upper limit of the thermostat
setting range to be electronically limited. Press +
until Option 30 is displayed, use V and Λ to select
required setting.
Setting
40 - 5°C (Factory setting is 30°C)
Option 31 - Set lower limit of temperature range
This allows the lower limit of the thermostat
setting range to be electronically limited. Press +
until Option 31 is displayed, use V and Λ to select
required setting.
Setting
5 - 40°C (Factory setting is 5°C)
Option 32 - Enable Off at lower limit
This enables an OFF function to be selected if a set
point below the lower limit is selected. Press + until
V
Λ
Option 32 is displayed, use
and
to select required
setting.
Setting 0 Disabled
Setting 1 Enabled (factory setting)
Option 33 - Enable On at upper limit
This enables an ON function to be selected if a set
point above the upper limit is selected. Press + until
V
Λ
Option 33 is displayed, use
and
to select required
setting.
Setting 0 Disabled (factory setting)
Setting 1 Enabled
8