English
Interface to the protetion device
Fiber optic cable (FO)
FO connector type
Optical wavelength
Baud rate
Receiver sensitivity (peak)
optical power for high-level
optical power for für low-level
Optical Power Budget
Bridgeable distance
Laser Class 1 according to EN 60825-1/-2
Receiver sensitivity (peak)
50/125 μm, NA
62.5/125 μm, NA
100/140 μm
200 μm HCS
1) Numeric apertur (NA) = sin (lauch angle)
2) This fibre optic cable type can be used as an alternative to the types described in the
manual.
68
Downloaded from
www.Manualslib.com
min.
1)
= 0.2
-19.8 dBm
1)
= 0.275
-16.0 dBm
2)
1)
, NA
= 0.3
-10.5 dBm
2)
1)
, NA
= 0.37
-6.2 dBm
manuals search engine
7XV5662-0AD00/DD, 7XV5662-0AD01/DD
ST connector
λ = 820 nm
512 kBit/s
Max. -40 dBm
Min. -24 dBm
Min. 4.2 dB for 50/125 μm, NA1) = 0.2
Min. 8 dB for 62.5/125 μm, NA1) = 0.275
Max. 1.5 km (For multi mode fibre, calculate
with a attenuation of 3 dB/km)
When using glass fiber 62.5/125 μm and
50/125 μm
typ.
-15.8 dBm
-12.0 dBm
-6.5 dBm
-3.7 dBm
C53000-B1174-C205-2
max.
-12.8 dBm
-9.0 dBm
-3.5 dBm
+1.8 dBm