Power supply: The auxiliary voltage must be applied at the 2-pole screw terminal
(DC 24 V to 250 V, AC 110 V to 230 V). The permissible values and tolerances can be
found in the Technical Data (Page 67). The grounding connection above must be
connected to the protective conductor (ground).

Connection Instructions

Screw terminals of the terminal blocks
The terminal screws are slotted screws that can be turned with a 0.3 mm × 3.5 mm or
0.6 mm × 3.5 mm screwdriver.
The following connections are present (s. Figure 21):
Connection block for the signals E1/T1 and screen S: 5-pole (for 7XV5662-0AD00)
Connection block for the signals E1: 2x BNC connection (for 7XV5662-0AD00)
Connection block for the signal GOK(DR): 3-pole
Connection block for the auxiliary voltage U
Figure 21 Terminal blocks
Strip the connecting wires to a length of 9 mm, insert them into the screw terminals as far as
they will go in, and secure them so that they will not slip out while tightening the screw. After
tightening the screws, verify that the wires to the terminals are tightly connected.
50
Downloaded from
www.Manualslib.com
manuals search engine
7XV5662-0AD00/DD, 7XV5662-0AD01/DD
: 2-pole
N
C53000-B1174-C205-2