The following figure shows the jumpers of the RS232/RS485 interface.
Wiring for termination = ON.
Figure 31 Jumpers of the termination resistances when using the RS485 interface
On delivery, the jumper for the bus termination is set to OFF.
Settings in the protection device
In SIPROTEC 4 protection devices (7SD52, 7SD610, 7SA52 or 7SA6) and in the SIPRO-
TEC 5 protection devices, the protection interface enables the communication with the
opposite protection device must be configured to "enabled". The transmission rate must be
set in both devices to the same value. For the synchronous mode the transmission rate must
be set to 512 kBit/s (Comm.-Converter 512 kBit/s) at the protection device.
Closing the cover of the CC-2M
After changing the jumper settings secure the cover of the converter with the 6 screws and
apply the auxiliary voltage again.