Herunterladen Diese Seite drucken

ABB DPA UPSCALE RI 10 Bedienungsanleitung Seite 128

Werbung

10.12.2 SINGLE FEED INPUT
Cable Sections and Fuse Ratings recommended. Alternatively, local standards to be respected
Fuse
Cable A
Cable E
Fuse E
Frame
M1
10.12.3 SINGLE FEED INPUT / Cable Sections
Input 3x400V/230V
Enclosure
Load
in KW
type
Fuse A
(Agl/CB)
Upscale RI 10
20
3x40A
Upscale RI 11
20
3x40A
Upscale RI 12
20
3x40A
Upscale RI 20
40
3x80A
Upscale RI 22
40
3x80A
Upscale RI 24
40
3x80A
Upscale RI 40
80
3x160A
n.a = not allowed
A
MAINS 3x400/230V
F1 F2
Rectifier
Inverter
Static Switch
M2
Maintenance Bypass IA1
Cable D
Load 3x400/230 V
Cable A
Max. Input Current
2
(mm
)
with battery
charging (A)
(IEC 60950-1)
5x6
5x6
5x6
5x16
5x16
5x16
5x50
04-3006_S10_ABB_TDS_DPA_UPScale_RI_EN_140102.DOC
STANDARD VERSION (SINGLE FEED INPUT)
F1 F2
Rectifier
Inverter
Static Switch
Output 3x400V/230V
@ cosphi 1.0
Cable D
2
(mm
)
(IEC 60950-1)
27
5x6
27
5x6
27
5x6
68
5x16
68
5x16
68
5x16
136 A
5x50
Modifications reserved
Battery
Cable E (mm
Only for external Batteries
Fuse E
I nom
+ / N / -
(A)
(Agl/CB)
Com.
Battery
29 A
3x63A
n.a
29 A
3x63A
n.a
29 A
3x63A
n.a
58 A
3x100A *1
3x25 *1
58 A
3x100A *1
n.a
58 A
3x100A *1
n.a
116 A
3x224A*1
3x95 *1
*1 only valid for common battery use
Section-10
2
)
+ / N / -
Sep. Battery
3x10
n.a
n.a
2x(3x10)
n.a
n.a
4x(3x10)
Page 15/16 ABB

Werbung

loading