10.5 OUTPUT CHARACTERISTICS
Module type
Output rated apparent power (
Output rated active power (
Output nominal current (In)
at 230VAC ph-N and cosphi 1.0
Output Rated Voltage
Output Voltage Stability
Output Voltage Distortion
Output Frequency
Output Frequency Tolerance
Efficiency AC-AC (at cosphi 1.0)
(tolerance +/- 0.5% applies on all figures)
Bypass operation
Permissible Unbalanced Load
(All 3 phases regulated independently)
Phase Angle Tolerance
(With 100 % Unbalanced load)
Overload Capability on Inverter
Output short capability on inverter (RMS)
Output short capability on static bypass
(RMS)
Static bypass transfer time:
inverter  bypass / bypass  inverter / in
eco-mode
10.5.1 GRAPH:
100
95
90
85
80
75
70
unit
kVA
cosphi 0.8)
KW
cosphi 1.0)
A
V
%
%
Hz
%
%
%
°
%
A
A
ms
AC – AC EFFICIENCY with Linier load @ cosphi 1
Efficiency up to 1 % higher with output PF cosphi 0.8
Details refer to paragraph 10.7 Environmental Characteristics
Linear Load (cosphi=1)
%
95
94.5
UPS Module 10/20kW
25
50
04-3006_S10_ABB_TDS_DPA_UPScale_RI_EN_140102.DOC
UPScale M 10
10
10
14.5
3x380/220V or 3x400/230V or 3x415/240V
Static:
Dynamic (Step load 0%-100% or 100%-0%)
With Linear Load
With Non-linear Load (EN62040-3:2001)
50 Hz or 60 Hz
Synchronized with mains
(selectable for bypass operation)
Free running
Load
:
100%
M20&M10 :
95.5
At Nominal Input voltage of 3x400 V
or 190 V to 264 V ph-N
100%
< 2
125 % load
150 % load
3.0xIn during 40 ms
10xIn during 20 ms
<1 / <5 / <6
95.5
95.5
75
100
Modifications reserved
UPScale M 20
20
20
29
or < +/- 4 %
75%
50%
25%
95.5
95
94.5
2.25xIn during 40 ms
Load %
Page 7/16 ABB
Section-10
< +/- 1%
< +/- 4%
< 1.5%
< 3%
< +/- 2 %
+/- 0.1 %
+/- 15%
10 min.
60 sec.