10.6 ENVIRONMENTAL CHARACTERISTICS
Module type
Module rated power
Operation temperature
Ambient Temperature for Batteries (recommended)
Storage Temperature
Battery Storage Time at Ambient Temperature
Max. altitude (above sea level) without de-rating
De-rating factor for use at altitudes above 1000m
sea level according (IEC 62040-3)
Relative Air-humidity
UPS Positioning
Input and Output Power Cabling
Efficiency AC-AC up to (at cosphi 1.0)
(tolerance +/- 0.5% applies on all figures)
Efficiency with Linear Load at cosphi =0.8 ind
Efficiency Non-linear Load (IEC/EN 6240-3)
Eco-Mode efficiency at 100% load
10.7 STANDARDS
Safety
Electromagnetic Compatibility
EMC Classification,
Emission Class
Immunity Class
Performance
Product certification
Degree of protection
EN 62040-1-1, EN 60950-1
EN 61000-6-4 Prod.standard: EN 62040-2
EN 61000-6-2 Prod.standard: EN 62040-2
EN 61000-4-2, EN 61000-4-3 - EN 61000-4-4 - EN 61000-4-5 - EN 61000-4-6
C3
C3
IEC/EN 62040-3
CE
IP 20
04-3006_S10_ABB_TDS_DPA_UPScale_RI_EN_140102.DOC
Modifications reserved
unit
UPScale M 10
kW
10
°C
0 - 40
°C
20 - 25
°C
-25 - +70
Max. 6 months
m/feet 1000 / 3300ft
(meter / feet) above sea level
1500 / 4850
2000 / 6600
m/feet
2500 / 8250
3000 / 9900
Max. 95% (non-condensing)
See chapter 10.11
From the bottom on the front
Load
:
100 %
%
M20&M10 :
95.5%
Typically up to 1 % higher of above values
Typically up to 1 % lower of above values
%
98 %
Section-10
UPScale M 20
20
De-Rating Factor for Power
0.95
0.91
0.86
0.82
75 %
50%
25%
95.5%
95%
94.5%
Page 9/16 ABB