10.12 WIRING AND BLOCK DIAGRAMS FOR ALL FRAMES AND MODULES
The customer has to supply the wiring to connect the UPS to the local power source. The installation inspection
and initial start up of the UPS and extra battery cabinet must be carried out by a qualified service personnel such
as a licensed service engineer from the manufacturer or from an agent authorized by the manufacturer.
More details and procedure are mentioned in the user manual.
10.12.1 TERMINAL CONNECTIONS OVERVIEW
FRAME TYPE
Battery Earth
Terminals (T)
PE
Connection Bar (B)
UPScale RI 10
16/25mm
UPScale RI 11
n.a.
UPScale RI 12
n.a.
UPScale RI20
16/25mm
UPScale RI 22
n.a.
UPScale RI 24
n.a.
UPScale RI40
50 mm
n.a. = not allowed
UPScale RI 11, RI 12, RI 22, RI 24 (on rear site)
Input
Output
UPScale RI 10 (on rear site)
Batt.
Input
Output
UPScale RI 40 (on rear site)
Batt.
Separate. Battery
(+ / N / - )
2
2
(T)
3 x 10/16mm
(T)
n.a.
n.a.
2x
2
(T)
2
(3 x 10/16mm
) (T)
n.a.
n.a.
4x
2
(T)
2
(3 x 10/16mm
) (T)
Input
Output
04-3006_S10_ABB_TDS_DPA_UPScale_RI_EN_140102.DOC
Common
Input Bypass
Battery
3+N
(+ / N / - )
n.a
n.a.
4 x 10/16 mm
n.a.
3 x M5 (B)
4 x 16/25 mm
n.a.
n.a.
3 x 50 mm
3 x M6 (B)
+ N 70/95 mm
(T)
UPScale RI 20 (on rear site)
Batt.
Input
Output
Modifications reserved
Input Rectifier
3+N+PE
2
2
(T)
5 x 10/16 mm
(T)
2
2
(T)
5 x 16/25 mm
(T)
2
2
3 x 50 mm
(T)
(T)
2
2
+ N 70/95 mm
(T)
2
+PE 50 mm
(T)
Section-10
Output load
3+N+PE
2
5 x 10/16 mm
(T)
2
5 x 16/25 mm
(T)
2
3 x 50 mm
(T)
2
+ N 70/95 mm
(T)
2
+PE 50 mm
(T)
Page 14/16 ABB