Herunterladen Diese Seite drucken
Eaton NRX Serie Montageanweisung
Eaton NRX Serie Montageanweisung

Eaton NRX Serie Montageanweisung

Neutralwandler
Vorschau ausblenden Andere Handbücher für NRX Serie:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Instruction Leaflet
Instructions for Series NRX Neutral
Current Sensor – Type RF
Instructions apply to:
Series NRX, Type RF Frame
IEC, IZMX40
4000 NRX RF DRAWOUT SUBTITLE IMAGE (12/15/2010)
(1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE PERMITTED TO WORK
ON THE EQUIPMENT.
(2) ALWAYS DE-ENERGIZE PRIMARY AND SECONDARY CIRCUITS IF A CIRCUIT
BREAKER CANNOT BE REMOVED TO A SAFE WORK LOCATION.
(3) DRAWOUT CIRCUIT BREAKERS SHOULD BE LEVERED (RACKED) OUT TO THE
DISCONNECT POSITION.
(4) ALL CIRCUIT BREAKERS SHOULD BE SWITCHED TO THE OFF POSITION AND
MECHANISM SPRINGS DISCHARGED.
FAILURE TO FOLLOW THESE STEPS FOR ALL PROCEDURES DESCRIBED IN THIS
INSTRUCTION LEAFLET COULD RESULT IN DEATH, BODILY INJURY, OR PROPERTY
DAMAGE.
THE INSTRUCTIONS CONTAINED IN THIS IL AND ON PRODUCT LABELS HAVE TO
BE FOLLOWED. OBSERVE THE FIVE SAFETY RULES:
– DISCONNECTING
– ENSURE THAT DEVICES CANNOT BE ACCIDENTALLY RESTARTED
– VERIFY ISOLATION FROM THE SUPPLY
– EARTHING AND SHORT-CIRCUITING
– COVERING OR PROVIDING BARRIERS TO
ADJACENT LIVE PARTS
DISCONNECT THE EQUIPMENT FROM THE SUPPLY. USE ONLY AUTHORIZED
SPARE PARTS IN THE REPAIR OF THE EQUIPMENT. THE SPECIFIED MAINTENANCE
INTERVALS AS WELL AS THE INSTRUCTIONS FOR REPAIR AND EXCHANGE MUST
BE STRICTLY ADHERED TO PREVENT INJURY TO PERSONNEL AND DAMAGE TO
THE SWITCHBOARD.
IL01301046E
• WARNING
• WARNING
effective September 2013
Series NRX

Werbung

loading

Inhaltszusammenfassung für Eaton NRX Serie

  • Seite 1 Instruction Leaflet IL01301046E effective September 2013 Series NRX Instructions for Series NRX Neutral Current Sensor – Type RF Instructions apply to: Series NRX, Type RF Frame IEC, IZMX40 4000 NRX RF DRAWOUT SUBTITLE IMAGE (12/15/2010) • WARNING (1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE PERMITTED TO WORK ON THE EQUIPMENT.
  • Seite 2 [13,46] 1.50 [38,1] 1.002 [25,44] 8X ( .463 -.417) (11.76-10.6) (3.937) [100] 3X (.984) [24,99] [12,5] (1.063) (1.574 ) (.787 ) [27] [39,98] [19,99] (2.637 ) [66,98] (3.700 ) [93,98] All dimensions in inch (mm). Figure 1. Dimensions. EATON www.eaton.com...
  • Seite 3 Using a low voltage (0-24v) high current AC source, apply a test current POWER SYSTEMS. ALWAYS TURN OFF POWER SUPPLYING CIRCUIT BREAKER of 125% of the ground fault pick-up setting through one phase of the BEFORE CONDUCTING TESTS. TEST OUT OF THE CELL, IF POSSIBLE. EATON www.eaton.com...
  • Seite 4 Resistor (if required) Resistor (if required) Figure 4. Connections for Ground Fault Figure 5. Connections for Ground Fault Figure 6. Connections for Ground Fault Trip Test No-Trip Test with a 4 Wire System No-Trip Test with a 3 Wire System EATON www.eaton.com...
  • Seite 5 Instructions for Series NRX Neutral Instruction Leaflet IL01301046E Current Sensor – Type RF effective September 2013 EATON www.eaton.com...
  • Seite 6 Current Sensor – Type RF effective September 2013 Disclaimer of warranties and limitation of liability In no event will Eaton be responsible to the purchaser or user in The information, recommendations, descriptions, and safety contract, in tort (including negligence), strict liability, or otherwise notations in this document are based on Eaton Corporation’s...
  • Seite 7: Die Montageanweisung Ist Für Folgende Baugrößen Gültig

    Instruction Leaflet IL01301046E gültig ab September 2013 Series NRX Montageanweisung für Series NRX Neutralwandler - Baugröße RF Die Montageanweisung ist für folgende Baugrößen gültig: Series NRX, Type RF Frame IEC, IZMX40 • WARNUNG 4000 NRX RF DRAWOUT SUBTITLE IMAGE (12/15/2010) (1) DIE INSTANDHALTUNG DARF NUR DURCH ENTSPRECHEND ELEKTRONTECHNISCH QUALIFIZIERTES PERSONAL ERFOLGEN.
  • Seite 8: Abschnitt 1: Installation Des Neutralwandlers

    [13,46] 1.50 [38,1] 1.002 [25,44] 8X ( .463 -.417) (11.76-10.6) (3.937) [100] 3X (.984) [24,99] [12,5] (1.063) (1.574 ) (.787 ) [27] [39,98] [19,99] (2.637 ) [66,98] (3.700 ) [93,98] All dimensions in inch (mm). Abbildung 1. Abmessungen EATON www.eaton.com...
  • Seite 9 Funktionsprüfung nicht aus nur Strom durch den Neutralwandler zu DIE GEFAHR EINES ELEKTRISCHEN SCHLAGS ODER EINES ELEKTROBRANDS. leiten, um den Erdschlussschutz zu prüfen. SCHALTEN SIE VOR DURCHFÜHRUNG DER PRÜFUNGEN IMMER DEN SCHALTER FÜR DIE STROMVERSORGUNG AB. ENTFERNEN SIE DEN SCHALTER WENN MÖGLICH IMMER AUS DER KASSETTE. EATON www.eaton.com...
  • Seite 10 Strombegrenzungs- Widerstand (falls Widerstand (falls Widerstand (falls nötig) nötig) nötig) Abbildung 4. Verbindungen für Abbildung 5. Verbindungen für Abbildung 6. Verbindungen für Erdschlussauslöseprüfungen (IEC) Erdschlussprüfung ohne Auslösung bei Erdschlussprüfung ohne Auslösung bei 4-poligen System (IEC) 3-poligen System (IEC) EATON www.eaton.com...
  • Seite 11 Montageanweisung für Series NRX Instruction Leaflet IL01301046E Neutralwandler - Baugröße RF gültig ab September 2013 EATON www.eaton.com...
  • Seite 12 Electrical Group 1000 Eaton Boulevard Cleveland, OH 44122 United States 877-ETN-CARE (877-386-2273) Eaton.com © 2013 Eaton Eaton is a registered Trademark. All Rights Reserved Printed in USA All other Trademarks are property of their Publication No. IL01301046EH01 respective owners. September 2013...

Diese Anleitung auch für:

Rf